-88-
(16) Emergency response operating mode
The emergency operation mode is a mode in which the unit is run in an emergency to respond to the trouble when
compressors (No. 1, No. 2) break down, making it possible to carry out a trouble reset using the remote control.
the
1) Starting the Emergency Operation Mode
Trouble occurs (Display the trouble code root and trouble code on the remote control).
Carry out trouble reset with the remote control.
If the trouble indicted in
above is of the kind that permits emergency operation (see the table below), initiate
retry operation.
a
If the trouble indicated in
above is of the kind where emergency operation is impossible (see the table below),
restart operation after carrying out the previous trouble reset (without entering the emergency operation mode).
If the same trouble is detected again during the retry operation in
above, carry out trouble reset once more
with the remote control, then try emergency operation starting corresponding to the contents of the trouble.
Table Emergency Operation Mode Patterns and Trouble Codes for which Emergency Operation is Possible or Impossible
Codes for which emergency operation is
possible.
Overcurrent protection
Error codes other than those at right.
Emergency Mode
Pattern
When a No. 1
Compressor Failure
Occurs
When No. 2
Compressor Failure
Occurs
Constant capacity
unit
Error (stop)
Trouble Codes for which
Emergency Operation is
Impossible
Trouble codes other than
those at left.
(a)High pressure/ low-
pressure pressure
error
1302
(b)Reverse phase error
4103
(c) Communication error
No communication with
variable capacity unit
(d)Constant capacity unit
power-off and LEV2
open
(e)Oil equalization circuit
irregularity
1559
Action
Emergency Operation with the
No. 2 and No. 3 Compressor
* After the retry operation, even if
there is a different trouble code
detected within <Inverter
Trouble> at left, press the button
and after resetting, start the unit
by emergency operation.
[Example]
4250 Reset Retry 4240
Reset Emergency
operation
Emergency Operation with the
No. 1 and No. 3 Compressor
Emergency response operation
with the variable capacity unit only
(No. 1 and No. 2 compressor).
Failed Compressor
External temp. (TH6)
Model 600 ~ 750
Notes
No.1
TH6
20˚C (cooling) or heating
60 ~ 70 %
No.2 + No.3 Compressors on
TH6 < 20˚C (cooling)
45 ~ 55 %
No.2 Compressor only
No.2
TH6
20˚C (cooling) or heating
65 ~ 75 %
No.1 + No.3 Compressors on
TH6 < 20˚C (cooling)
45 ~ 55 %
No.1 Compressor only
No. 3
Don’t care
80 ~ 90 %
No.1 + No.2 Compressors on
Caution
During emergency operation, only marked percentage of indoor units can be operated during emergency operation.
In case, more than marked percentage of indoor units are operated, over than the percentage of indoor units
would be on the stand-by mode.
1
1
1
3
2
3
4
Serial transmission trouble
0403
VDC sensor/circuit trouble
4200
Bus voltage trouble
4220
Radiator panel overheat
protection
4230
Overload protection
4240
4250
IPM Alarm output/
Bus voltage trouble/
Over Current Protection
Cooling fan trouble
4260
Thermal sensor trouble
(Radiator panel)
5110
IAC sensor/circuit trouble
5301
Содержание CITY MULTI PUHY-400YMF-C
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 149: ... 146 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...
Страница 207: ......
Страница 208: ......
Страница 209: ......