-159-
Checking code
Meaning, detecting method
Cause
Checking method & Countermeasure
4200 VDC
sensor/circuit
abnormality
(Variable
Capacity unit)
1
If VDC 304 V is detected just
before the inverter starts.
2
If VDC 750 V is detected just
before starting of and during
operation of the inverter.
1) Power supply voltage is abnor-
mal.
2) The wiring is defective.
3) The rush current prevention
resistors (R1, 5) are defective.
4) The electromagnetic contactor
(52C) is defective.
5) The diode stack (DS) is defective.
6) The reactor (DCL) is defective.
7) The INV board is defective.
•
Check if an instantaneous power
failure or power failure, etc. has
occurred.
•
Check if the voltage is the rated
voltage value.
Check 1, the connections, 2, contact
at the connectors, 3 tightening torque
at screw tightened portions, 4, wiring
polarities, 5, for broken wires, and 6,
for grounding in the following wiring.
TB1A~NF~TB1B, TB1B~DS~[52C,
R1, R5]~[C2, C3]~IPM Wiring
CNDC1 (G / A) ~ CNVDC (INV) Wir-
ing
*
Check if the wiring polarities are as
shown on the wiring diagram plate.
To judge failure of R1 and R5, go to
“Individual Parts Failure Judgment
Methods.”
To judge failure of the 52C, go to
“Individual Parts Failure Judgment
Methods.”
To judge failure of the DS, go to
“Individual Parts Failure Judgment
Methods.”
To judge failure of the DCL, go to
“Individual Parts Failure Judgment
Methods.”
If none of the items in 1) to 6) is
applicable, and if the trouble
reappears even after the power is
switched on again, replace the INV
board (when replacing the circuit
board, be sure to connect all the
connectors, ground wires, etc.
securely).
4210 Breaking of
overcurrent
(Variable
capacity unit)
1
If IDC
103 A peak is de-
tected during inverter opera-
tion.
2
If the voltage of the INV
board’s sensor circuit input is
what it should not normally be.
•
Check if an instantaneous power
failure or power failure, etc. has
occurred.
•
Check if the voltage is the rated
voltage value.
Check 1, the connections, 2, contact
at the connectors, 3 tightening torque
at screw tightened portions, 4, wiring
polarities, 5, for broken wires, and 6,
for grounding in the following wiring.
TB1A ~ DS ~ [52C, R1, R5] ~ [C2,
C3] ~ TRM Wiring
TRM ~ CNVDC Wiring
TRM ~ Compressor Wiring
[CN2-1, CN2-2, CN2-3, CN3]
~ TRM Wiring
*
Check if the wiring polarities are as
shown on the wiring diagram plate.
*
Check the coil resistances and in-
sulation resistance of the compres-
sor.
Go to “Treatment of Inverter/Compres-
sor Related Trouble.”
1) The power supply voltage is
abnormal.
2) The wiring is defective.
3) The inverter/compressor is
defective.
Содержание CITY MULTI PUHY-400YMF-C
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 149: ... 146 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...
Страница 207: ......
Страница 208: ......
Страница 209: ......