-106-
[2] Operation Flow Chart
(1)
Outdoor unit (Cooling, heating modes)
Note: 1
For about 2 minutes after turning on power source, address and group information of outdoor unit, indoor unit, and remote
controller are retrieved by remote controller, during which “HO” blinks on and off on remote controller. In case indoor unit is
not grouped to remote controller, “HO” display on remote controller continues blinking even after 2 minutes after turning on
power source.
Note: 2
Two trouble modes included indoor unit side trouble, and outdoor unit side trouble. In the case of indoor unit side trouble,
error stop is observed in outdoor unit only when all the indoor units are in trouble. However, if one or more indoor units are
operating normally, outdoor unit shows only LED display without undergoing stop.
Note : 3
Operation mode conforms to mode command by indoor unit. However, when outdoor unit is in cooling operation, the
operation of indoor unit will be prohibited even by setting a part of indoor units under operation, or indoor unit under
stopping or fan mode to heating mode. Reversely when outdoor unit in heating operation, the same condition will be
commenced.
YES
NO
YES
NO
YES
YES
NO
NO
2
Normal operations
Trouble observed
Stop
“HO” blinks on the remote control-
ler
Oil return LEV, SC coil LEV
fully closed
Variable capacity unit
1. 52C1, 52C2 OFF
2. Inverter output 0 Hz
3. Outdoor fan Stop
4. All solenoid valve OFF
5. LEV1, SLEV full closed.
Constant capacity unit
1. 52C OFF
2. Outdoor fan Stop
3. All solenoid valve OFF
4. LEV1, LEV2 full closed.
Breaker
turned on
Error code blinks on the
outdoor controller board
Start
Set indoor
address No. to
remote controller
Operation
command
Operation
mode
Error mode
52C ON
Operation
mode
Heating opera-
tions
Cooling opera-
tions
Operation mode command to indoor unit controller
Error stop
Error command to indoor
unit
Note: 1
Note: 2
Cooling, Heating
Fan
Note: 3
Error code blinks on the
remote controller
Содержание CITY MULTI PUHY-400YMF-C
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 149: ... 146 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...
Страница 207: ......
Страница 208: ......
Страница 209: ......