-174-
Checking
code
7102
7105
7111
Meaning, detecting method
Cause
Checking method & Countermeasure
Connected unit count over
Address setting error
•
Erroneous setting of OC unit
address
Remote control sensor error
Error not providing the tempera-
ture designed to remote control-
ler sensor.
Trouble source:
Indoor unit
2) Disconnection of transmission
wiring at Outdoor unit.
3) Short circuit of transmission line in
case of 2) and 3), remote controller
displays “HO”.
4) When PUHN is connected with
SW4-6=OFF.
5) When PUHN is not connected with
SW4-6=ON.
1) Setting error of Outdoor unit ad-
dress.
The address of Outdoor unit is not
being set to 51~100.
1) In case when the old type remote
controller for M-NET is used and the
remote controller sensor is de-
signed on indoor unit. (SW1-1
turned ON)
d) Check for the model total (capacity code total)
of indoor units connected.
Check that the address of OC unit is being set to
51~100.
Reset the address if it stays out of the range, while
shutting the power source off.
a) Replace the old remote controller by the new
remote controller.
Trouble source:
Indoor unit
a) Check that the power has not been cut-off due
to the power supply of transmission booster
being connected to the indoor unit switch.
(The air conditioner will not operate correctly if
the power supply of transmission booster is
not turned on.)
→
Reset the outdoor unit power supply.
The indoor unit will not operate
because it is not correctly con-
nected to the outdoor unit of the
same refrigerant system.
1) The transmission booster is defec-
tive, has disconnected wires, or the
power has been cut-off.
2) The transmission booster and out-
door unit power supplies have been
cut-off.
7110
Use the same type of refrigerant in all units
included in the system.
Different Refrigerant unit
connected error
(See Table 1)
7130
If different units within one system are using different types of refrigerant as shown in table 1 below, the system will not
operate correctly.
Table1
Refrigerant type
Example 1
Example 2
Example 3
R407C
R407C
R22
R407C
R22
R407C
R22 only
–
–
Variable capacity unit
Constant capacity unit
Indoor units
Содержание CITY MULTI PUHY-400YMF-C
Страница 15: ... 12 FANCON board G A board CNFAN CNFC2 CNPOW CNE CNDC1 CN15V1 CNDR1 CNIPM1 ...
Страница 16: ... 13 Y C board SNB board ...
Страница 17: ... 14 RELAY board CNRT2 CNCH CN52C2 CN52F CN51C2 CNOUT2 ...
Страница 19: ... 16 CONT board CNTR SWU2 SWU1 SW3 SW2 CNS1 M NET transmission CNFC1 CN20 Power supply 1 N 3 L1 ...
Страница 20: ... 17 FANCON board CNW CNV CNU CNFC2 ...
Страница 149: ... 146 Motor Compressor G A board Red U V W N P White Black Black Capacitor C2 C3 Red IPM ...
Страница 207: ......
Страница 208: ......
Страница 209: ......