MIV V5 Heat Recovery DC Inverter R410A
56
Specifications
&
Performances
6. Electric characteristics
Model
Units Power
supply
Compressor
OFM
Hz
Voltage
(V)
Min.
(V)
Max.
(V)
MCA
(A)
TOCA
(A)
MFA
(A)
MSC
(A)
RLA
(A)
kW
FLA
(A)
MVUR252B-VA3
50/
60
380~415 342 440 18.4 20.8 25
- 17.4 0.42 3.6
MVUR280B-VA3
50/
60
380~415 342 440 20.6 22.1 25
- 17.4 0.42 3.6
MVUR335B-VA3
50/
60
380~415 342 440 21.8 22.8 25
- 17.4 0.42 3.6
MVUR400B-VA3
50/
60
380~415 342 440 27.9 31.8 35
-
17.4+
10.5
0.71 5.9
MVUR450B-VA3
50/
60
380~415 342 440 33.4 32.8 35
-
17.4+
10.5
0.71 5.9
The current value of combination unit is the total value of each basic model (refer to Units Combination Table in
Part1)
For example: 46HP=16HP+16HP+14HP
Power current: MCA=33.4+33.4+27.9=94.7
TOCA=32.8+32.8+31.8=97.4
MFA=35+35+35=105
Compressor: RLA=(17.4+10.5)+ (17.4+10.5)+ (17.4+10.5)=83.7
OFM: FLA=5.9+5.9+5.9=17.7
Notes:
1. RLA is based on the following conditions, Indoor temp. 27°C DB/19°C WB, Outdoor temp. 35°C DB
2. TOCA means the total value of each OC set.
3. MSC means the Max. current during the starting of compressor.
4. Voltage range.
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits.
5. Maximum allowable voltage variation between phases is 2%
6. Selection wire size based on the larger value of MCA or TOCA
7. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker).
MCA:
Min. Circuit Amps. (A)
TOCA:
Total Over-current Amps. (A)
MFA:
Max. Fuse Amps. (A)
MSC:
Max. Starting Amps. (A)
RLA:
Rated Load Amps. (A)
OFM:
Outdoor Fan Motor.
FLA:
Full Load Amps. (A)
KW:
Rated Motor Output (KW)