DM14-01.01.18en
MIV V5 Heat Recovery DC Inverter R410A
Installation Procedure
112
Outdoor unit branch pipe assembly
Table 3: Outdoor unit connection pipe selection (g1, g2, g3, g4, G1, G2) Unit: mm
Pipe
Low pressure gas pipe
High pressure gas pipe
Liquid pipe
g1,g2,g3,g4
8/10/12HP
Φ
22.2
Φ
19.1
Φ
12.7
14/16HP
Φ
28.6
Φ
22.2
Φ
15.9
G1
Φ
34.9
Φ
28.6
Φ
19.1
G2
Φ
41.3
Φ
34.9
Φ
22.2
Table 4: Outdoor unit branching pipe assembly selection (L, M, N)
Outdoor unit quantity
Parallel connect with the branch pipes
2 units
L: FQZHW-02SB
3 units
L+M: FQZHW-03SB
4 units
L+M+N: FQZHW-04SB
Indoor unit auxiliary pipe selection
Table 5: Indoor unit auxiliary pipe between MS and downstream branch joint selection (a, g, j, k)
Capacity of indoor unit
kW
Gas pipe (mm)
Liquid pipe (mm)
Available branching pipe
A<16.6
Φ
15.9)
Φ
9.53) FQZHN-01D
Table 6: Indoor unit auxiliary pipe from indoor unit to the nearest branch joint or direct connected MS
selection (b, c, d, e, f, h, i, l, m, n, p, q, r) Unit: mm
Capacity of indoor unit
kW
The pipe length from indoor unit to the nearest
branch joint or direct connected MS
≤
10m
The pipe length from indoor unit to the nearest
branch joint or direct connected
MS
>
10m
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
A<5.6
Φ
12.7
Φ
6.35
Φ
15.9
Φ
9.53
5.6
≤
A<16
Φ
15.9
Φ
9.53
Φ
19.1
Φ
12.7
Illustration
Outdoor
unit Qty.
2 units
3 units
4 units
Main pipe
L
g1
g2
L
M
g1
g2
G1
g3
Main pipe
L
M
N
G2
G1
g1
g2
g3
g4
Main pipe