DM14-01.01.18en
MIV V5 Heat Recovery DC Inverter R410A
Installation Procedure
114
The downstream indoor units of L11 are N8, N9 and N10, which capacity is 2.8+5.6×2=14 kW. Refer to table
1, the indoor unit main pipe L11 is
Φ
19.1/
Φ
15.9 /
Φ
9.53, select MS02/N1-C for MS6.
The downstream indoor units of L9 are N5~N10, which capacity is 14+5.6×2+7.1×2+2.8=42.2 kW. Refer to
table 1, the indoor unit main pipe L9 is
Φ
28.6/
Φ
22.2/
Φ
12.7, the branch pipe assembly E is FQZHN-03SB.
The downstream indoor units of L8 are N11~N13, which capacity is 14×2+5.6=33.6 kW. Refer to table 1, the
indoor unit main pipe L8 is
Φ
28.6/
Φ
22.2/
Φ
12.7, select MS04/N1-C for MS7.
The downstream indoor units of L7 are N5~N13, which capacity is 14×3+7.1×2+5.6×3+2.8=75.8 kW. Refer
to table 1, the indoor unit main pipe L7 is
Φ
34.9/
Φ
28.6/
Φ
19.1, the branch pipe assembly D is
FQZHN-04SB.
The downstream indoor units of L1 are N1~N13, which capacity is 14×4+7.1×4+5.6×3+2.8×2=106.8 kW.
Refer to table 1, the indoor unit main pipe L1 is
Φ
41.3/
Φ
34.9/
Φ
19.1, the branch pipe assembly A is
FQZHN-05SB.
4. Select main pipe: L1
For the capacity of outdoor unit is 38HP, the equivalent length of all pipes in this system is larger than 90m,
refer to table 2, the main pipe L1 is
Φ
41.3/
Φ
34.9/
Φ
22.2, the branch pipe assembly A is FQZHN-05SB.
As the main pipe L1 is selected as
Φ
41.3/
Φ
34.9/
Φ
19.1 from step 3, and
Φ
41.3/
Φ
34.9/
Φ
22.2 from step 4, we
finally select the larger pipe
Φ
41.3/
Φ
34.9/
Φ
22.2 as main pipe L1.
5. Outdoor unit connection pipe (g1, g2, g3, G1,L+M) selection (refer to table3, table 4)
The pipe g1 is connected to 10HP outdoor unit. Refer to table3, the diameter of g1 is
Φ
22.2 /
Φ
19.1/
Φ
12.7
The pipe g2 is connected to 12HP outdoor unit. Refer to table3, the diameter of g2 is
Φ
22.2 /
Φ
19.1 /
Φ
12.7
The pipe g3 is connected to 16HP outdoor unit. Refer to table3, the diameter of g3 is
Φ
28.6/
Φ
22.2 /
Φ
15.9
The upstream outdoor unit quantity of G1 is two. Refer to table3, the diameter of G1 is
Φ
34.9/
Φ
28.6/
Φ
19.1
The quantity of combined outdoor units is three. Refer to table4, the outdoor branch assembly is L+M:
FQZHW-03SB
Note: For the detail dimension and installation information pipe, please read the branch pipe installation manual carefully.