Troubleshooting
4.8 H0: Communication error between main control chip and inverter driver chip
H1: Communication error between main control chip and communication chip
The error only display on faulty unit, all the ODU will be standby.
Note:
1. How to check whether power supply for transformer is abnormal
①
Check the voltage of 8(CN31), 9(CN33) and 24(CN35) terminals. The normal voltage of 8(CN31) and 9(CN33) terminals should
be 220V, the voltage between “GND” and “5V” of 24(CN35) terminal should be 5V, the voltage between “GND” and “12 of
24(CN35) terminal should be 12. If the voltage is out of the range, the power supply for main PCB and transformer is abnormal.
2. How to check whether the transformer is disabled
②
The voltage between upper tow pins of 18(CN32) terminal is AC 13.5V; the voltage between under tow pins of 18(CN32) terminal
is AC 9V. The voltage between upper tow pins of 19(CN34) terminal is AC 14.5V; the voltage between under tow pins of 19(CN34)
terminal is AC 14.5V
H0/H1
Power supply for main PCB and
transformer is abnormal
①
The transformer is damaged
②
Remove the interference
No
No
No
Yes
There has electromagnetic interference
nearby the unit. Such as High-frequency
transmitter or other high strength radiation
device
Replace the transformer
Provide normal power supply
Yes
Yes
CN34: Power output
of No.2 transformer
Outdoor main PCB
is damaged
Replace the outdoor
main PCB
No
CN32: Power output
of No.2 transformer
13.5
V
9
V
14.5
V
14.5
V