DM14-01.01.18en
MIV V5 Heat Recovery DC Inverter R410A
187
Troubleshooting
4.20 PL/C7: Temperature protection of main inverter module
When the temperature of inverter module is over 80
o
C, it will display PL protection.
If the system display three times PL protection in 100 minutes, the system will stop and display C7 error code.
When the system displays C7 error code, the system can resume only by restarting the machine.
1. How to check whether the temperature sensor is short circuit or disabled
①
:
Using a multimeter to measure resistance, if the resistance is too small, the sensor is short circuit, if the resistance in certain
temperature is not consistent with attached table 2, the sensor is disabled
The screw between inverter
module and radiating fin is
loose
Outdoor main PCB is damaged
Replace the outdoor
main PCB
PL/CL
Temperature sensor of main
inverter module sensor is short
circuit or disabled
①
.
Replace the sensor
Yes
No
No
Yes
Tighten the screw,
make sure the
inverter module is
closed to the
radiating fin
Yes