Troubleshooting
4.5 E5: Voltage error
The error only display on faulty unit, all the ODU will be standby.
Note:
1. How to check whether the compressor is short circuit
①
:
The normal resistance value of inverter compressor among U V W is 0.7~1.5
Ω
, and infinity to earth. If the resistance value is out
of the range, the compressor is abnormal.
2. How to check whether the fan motor is short circuit
②
:
The normal value of DC fan motor coil among U V W is less than 10
Ω
, and the value of AC fan motor coil is from a few ohm to
hundreds of ohm for different fan motor model. If the measured value is 0
Ω
, the fan motor is short circuit.
3. How to check whether the inverter module is output error
③
:
Let PN and U V W of inverter module short circuit, then dial multimeter to buzzer file, if the multimeter is ring, the inverter module
is output error.
E5: Voltage error
Voltage of power supply is too high or
too low (the normal voltage between A
and N (B and N, C and N) should be
198V~242V)
Provide normal power supply
Check the high voltage circuit. Whether
the compressor is short circuit
①
, fan
motor is short circuit
②
, inverter module
is output error
③
, etc.
Replace the inverter module
or repair related parts
No
No
Yes
Yes
Outdoor main PCB
is damaged
Replace the outdoor
main PCB