![Midea MVUR252B-VA3 Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/midea/mvur252b-va3/mvur252b-va3_service-manual_1791261030.webp)
DM14-01.01.18en
MIV V5 Heat Recovery DC Inverter R410A
28
Specifications
&
Performances
CFM
8,830
8,830
Sound pressure level
dB(A)
60
60
Connectable
indoor unit
Total capacity
%
50-130
50-130
Max. quantity
23
26
Outdoor unit
Net dimension (W×H×D)
mm
1250×1615×765
1250×1615×765
Packing (W×H×D)
mm
1305×1790×820
1305×1790×820
Net weight
kg
303
303
Gross weight
kg
322
322
Refrigerant
Type R410A
R410A
Factory charged
kg
13
13
Additional
refrigerant oil
Oil type
FVC68D
FVC68D
Oil charge
L
7
7
Throttle type
EXV EXV
Design pressure (Hi/Lo)
MPa 4.4/2.6
4.4/2.6
PSI 640/380
640/380
Refrigerant
piping
Liquid Pipe
in.(mm)
Ф
5/8(15.9)
Ф
5/8(15.9)
Low Pressure Gas Pipe
in.(mm)
Ф
1-1/8(28.6)
Ф
1-1/8(28.6)
High Pressure Gas Pipe
in.(mm)
Ф
7/8(22.2)
Ф
7/8(22.2)
High Pressure Gas Balance Pipe
in.(mm)
Ф
3/4(19.1)
Ф
3/4(19.1)
Oil Balance Pipe
in.(mm)
Ф
1/4(6)
Ф
1/4(6)
Ambient temp.
range
Cooling
o
C -5~48
-5~48
Heating
o
C -20~24
-20~24
Simultaneous Cooling and Heating
o
C -5~24
-5~24
Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27
℃
DB/19
℃
WB; Outdoor temperature 35
℃
DB/24
℃
WB.
Heating: Indoor temperature 20
℃
DB/15
℃
WB; Outdoor temperature 7
℃
DB/6
℃
WB.
Piping length: Interconnecting piping length is 7.5m, level difference is zero.
Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90m. When the total equivalent liquid
length is more than 90m, please refer to technical manual to choose the connection piping diameter.
Sound values are measured in a semi-anechoic room, at a position 1m in front of the unit and 1.3m above the floor.