MIV V5 Heat Recovery DC Inverter R410A
DM14-01.01.18en
Troubleshooting
162
Note:
1. Press the manual button on display board of indoor unit for 5 seconds, the communication address code of
indoor unit will display;
Codes are as follows:
Indicator light
Running
Timer
Fan/defend cold fan
Warning
Code 8 4
2
1
Buzzer
Communication address
Four LED display
Not warning
00---15
Normally on
Not warning
16---31
Flash
Warning
32---47
Normally on
Warning 48---63 Flash
For example:
Press the manual button for 5 seconds:
If the “Operation”,
“
Timer” and “DEF./FAN” lights are normally on and the buzzer is not warning, that means
the address code is 14=(8+4+2)
If the four LED lights are flash and the buzzer isn’t warning, the address code should plus 16, that means the
address code is 30=16+ (8+4+2)
If the “Operation”,
“
Timer” and “DEF./FAN” lights are normally on and the buzzer is warning, that means the
address code is 46=32+(8+4+2)
If the four LED lights are flash and the buzzer is warning, that means the address code is 62=48+ (8+4+2)
2. Press the manual button on display board of indoor unit for 10 seconds, the capacity code of indoor unit will
display;
Dial code
Capacity (×100W)
Capacity (Btu/h)
Capacity (HP)
0 22
7510
0.8
1 28
9550
1.0
2 36
12280
1.2
3 45
15350
1.6
4 56
19110
2.0
5 71
24230
2.5
6 80
27300
3.0
7 90
30710
3.2
8 112
38210
4.0
9 140
47770
5.0
A 160
54590
6.0
B 160
54590
6.0
C 160
54590
6.0
D 160
54590
6.0
E 160
54590
6.0
F 160
54590
6.0
For example