4.4 E4: Temperature senor (ambient temperature sensor T4, pipe temperature sensor T3/T5)
E7: Discharge temperature sensor error
The error only display on faulty unit, all the ODU will be standby.
E4/H7: Temperature sensor error
Temperature sensor port
on main PCB are loose
Fasten the temperature
sensor port
Temperature sensor is short circuit or
disabled (Using a multimeter to
measure resistance, if the resistance is
too small, the sensor is short circuit, if
the resistance in certain temperature is
not consistent with attached table 1,
the sensor is disabled)
Replace the sensor
No
No
Yes
Yes
Outdoor main PCB
is damaged
Replace the outdoor
main PCB