![Midea MVUR252B-VA3 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/midea/mvur252b-va3/mvur252b-va3_service-manual_1791261005.webp)
DM14-01.01.18en
MIV V5 Heat Recovery DC Inverter R410A
General Information
3
1.2 Flexible design
1.2.1 Wide capacity range
The outdoor units’ capacity range from 8HP to 64HP in 2HP increment. Maximum 64 indoor units with capacity
up to 130% of total outdoor units can be connected in one refrigeration system.
1.2.2 Wide operation range
The V4 Plus R series system operates stably at extreme temperatures ranging from -20°C(-4
o
F) to 48°C(118.4.
o
F)
1.2.3 Flexible piping design
1.2.4 High external static pressure
High static pressure propeller and optimized fan guard can adapt to various installation environments.
Midea now offers up to 60Pa*(0.24in.WG) external static pressure for customized applications
(60Pa(0.24in.WG) is available customized for the 8-12HP model; 40Pa(0.16in.WG) is available customized for
14-16HP). A standard 0-20Pa(0-0.08in.WG) function is equipped by default.
60 Pa
Piping length
Permitted value
Total pipe length
3280ft(1000m)
Max. actual pipe length
574ft(175m)
Max. equivalent pipe length
656ft(200m)
Equivalent piping length from the
farthest IDU to the first indoor
branch joint
131/295*ft(40/90*m)
Equivalent piping length from MS to
its farthest downstream indoor unit
131ft(40m)
Level difference between outdoor
unit and indoor unit
Outdoor unit is down: 361ft(110m)
Outdoor unit is up: 230ft(70m)
Level difference between indoor
units
98ft(30m)
* When the length is more than 40m, it needs to meet the specific
conditions according to the installation technical manual.