DM14-01.01.18en
MIV V5 Heat Recovery DC Inverter R410A
157
Troubleshooting
3. Error code table
Error code
Content
Note
E0
Communication error between outdoor units
Only display on the faulty slave unit, all the ODUs are in
standby.
E1
Phase sequence error
Display on the faulty unit, all the
ODUs
are in standby.
E2
Communication error between indoors and the
master unit.
Only display on the master unit, all the ODUs are in
standby.
E4
Outdoor ambient temperature sen
sor (T4) and
condenser pipe temperature sensor (T3/T5) erro
r
Display on the faulty unit, all the
ODUs
are in standby.
E5 Power
voltage
error
Display on the faulty unit, all the
ODUs
are in standby.
E7
Discharge temp sensor error
Display on the faulty unit, all the
ODUs
are in standby.
E8
Outdoor unit address is wrong
Only display on the faulty slave unit, all the ODUs are in
standby.
XE9
Driver model is mismatching
When X is 1, it means A system; 2 means B system
H0
Communication error between main control chip
and inverter driver chip
Display on the faulty unit, all the
ODUs
are in standby.
H1
Communication error between main control chip
and communication chip
Display on the faulty unit, all the
ODUs
are in standby.
H2
Quantity of outdoor unit decreased
Only display on the master unit, all the
ODUs
are in
standby.
H3
Quantity of outdoor unit increased
Only display on the master unit, all the
ODUs
are in
standby.
H4
P6 protection appears three times in 60 minutes
Display on the faulty unit, all the
ODUs
are in standby.
Cannot be recovered until re-power on.
H5
P2 protection appears three times in 60 minutes
Display on the faulty unit, all the
ODUs
are in standby.
Cannot be recovered until re-power on.
H6
P4 protection appears three times in 100 minutes
Display on the faulty unit, all the
ODUs
are in standby.
Cannot be recovered until re-power on.
H7
Quantity of indoor unit decreased
Only display on the master unit, all the
ODUs
are in
standby.
H8
High pressure sensor error
The discharge pressure Pc
≤
0.3MPa
H9
P9 protection appears three times in 60 minutes
Display on the faulty unit, all the
ODUs
are in standby.
Cannot be recovered until being power on again.
xHd
Slave units malfunction
X stands for corresponding slave unit
C7
PL protection appears three times in 100 minutes
Display on the faulty unit, all the
ODUs
are in standby.
Cannot be recovered until re-power on.
P1
High pressure protection
Display on the faulty unit, all the
ODUs
are in standby.
P2
Low pressure protection
Display on the faulty unit, all the
ODUs
are in standby.
XP3
Over current protection of inverter compressor
Display on the faulty unit, all the
ODUs
are in standby.
P4
Compressor discharge temp protection
Display on the faulty unit, all the
ODUs
are in standby.
P5
Condenser high temperature protection
Display on the faulty unit, all the
ODUs
are in standby.
XP6
Inverter module protection
When X is 1, it means A inverter module; 2 means B
inverter module
P9
Fan module protection
Display on the faulty unit, all the
ODUs
are in standby.
PL
Temperature protection of main inverter module
L0
Inverter module error
Display after P6 displaying for one minute