Page 132
Error message
Meaning of the error message Measures
Main
index
Sub
index
38
0
sercos prog.: SERCON
initialisation error
Technology module defective?
Replace the technology module.
If necessary, contact the Technical Support.
1
Sercos:
no technology module present
Technology module plugged in correctly?
Technology module defective?
Replace the technology module.
If necessary, contact the Technical Support.
2
Sercos:
defective technology module
Replace the technology module.
If necessary, contact the Technical Support.
3
Sercos:
S-0-0127: invalid data in S-0-
0021
Check the configuration (cyclic data for MDT and
AT).
Time slot calculation by the master.
4
Sercos:
S-0-0127: illegal IDNs in AT or
MDT
Check the configuration (cyclic data transfer).
5
Sercos:
S-0-0128: invalid data in S-0-
0022
Check the weighting settings.
Check the operating mode settings.
Check the internal/external angle encoder
settings.
6
Sercos:
S-0-0128: faulty weighting
parameters
Check the weighting settings.
7
Sercos:
Invalid IDN in S-0-0026 / S-0-
0027
Check the configuration of the signal status and
signal control word (S-0-0026 / S-0-0027).
8
Sercos:
error during the conversion
Check the weighting settings.
If necessary, contact the Technical Support.
9
Sercos:
SERCON 410b mode active
Technology module defective?
Replace the technology module.
Product Manual „Servo drives ARS 2100 SE“