Setup Time Zone
The time zone of the GPS receiver can be set up. These parameters will affect the
serial output lines and the time code (IRIG) outputs. The internal time zone of the
timeserver and the time of NTP will always be UTC. The time monitored in the main
menu will be the time of the NTP.
This menu lets the user enter the names of the local time zone with daylight saving
disabled and enabled, together with the zones´ time offsets from UTC. These
parameters are used to convert UTC to local time, e.g. MEZ = UTC + 1h and MESZ
= UTC + 2h for central Europe. The range of date daylight saving comes in effect can
be entered using the next two pages of the setup menu.
Beginning and ending of daylight saving may either be defined by exact dates for a
single year or using an algorithm which allows the receiver to re-compute the
effective dates year by year. The figures below show how to enter parameters in both
cases. If the number of the year is displayed as wildcards (´*´), a day-of-week must be
specified. Then, starting from the configured date, daylight saving changes the first
day which matches the configured day-of-week. In the figure below October 25th,
2008 is a Saturday, so the next Sunday is October 26th, 2008.
All changeover rules for the daylight saving like "the first/the second/the second to
last/the last Sunday/Monday etc. in the x-th month," can be described by the used
format "first specified day-of-week after a defined date".
If the number of the year is not displayed as wildcards the complete date exactly
determines the day daylight saving has to change (October 26th, 2008 in the figures
below), so the day-of-week does not need to be specified and therefore is displayed as
wildcards.
If no changeover in daylight saving is wanted, identical dates and times must be
entered in both of the submenus (DAYLIGHT SAV ON/OFF). After this a restart
should be done.
40
Serial Outputs
Setup COM 0
Setup COM 1
-> Time Zone <-
->Set Timezone<-
DL Sav ON
DL Sav OFF
DAYLIGHT SAV OFF
Date: 25.10.****
Day of week Sun
Time: 3:00:00
DAYLIGHT SAV OFF
Date: 25.10.2008
Day of week ***
Time: 3:00:00
Содержание M900
Страница 1: ...Technical Information Operating Instructions M900 GPS PZF Redundant SHS ...
Страница 21: ...Assembly with CN UB E 21 ...
Страница 48: ...48 ...
Страница 64: ...Configuration Ethernet 64 ...
Страница 69: ...Configuration Notification 69 ...
Страница 74: ...Configuration Security 74 ...
Страница 87: ...Configuration Local 87 ...
Страница 95: ...Configuration Statistics 95 ...
Страница 144: ...IRIG Standard Format 144 ...
Страница 145: ...AFNOR Standard Format 145 ...