Model: MTS200 (1U)
Doc. Ref. no. : m08/om/201
Issue no. : 03
User’s Manual
Page 186 of 195
Page 186 of 195
17 Troubleshooting
17.1 Unit not getting Power ON
Below mention, points need to be check to troubleshoot this problem.
1) Check Power input cable connected properly
2) Check Power input cable connected to respective terminal as described in section 14.1
3) Check Input power is available.
4) Check fuse is melted or not, if fuse is melted please contact masibus support department.
17.2 Wrong time at Unit Power ON
If the unit was kept in Power OFF conditions for the duration more than 15 days, as per
mentioned in section 8.2, the battery back of internal RTC will get discharged completely. As a
result, at unit Power ON, time displayed on LCD and time provided in all time outputs will be
according to default internal time till the unit gets LOCKED after GPS antenna is connected to
unit.
If the battery is discharged as per mentioned above, it is necessary to keep unit in Power ON
condition for duration mentioned in section 8.2, for full charging of internal battery. Full charging
is necessary to avoid possibility of wrong time output at unit Power ON.
17.3 masTER T-Sync Model MTS200 display time not as per Local time
If
mas
TER
T-Sync
Model MTS200 time on display, NGTS & T-format time output, all event
outputs is not as per Local time, the timezone offset w.r.t UTC may not be set as per required
time offset for the region/country where unit is installed. Please refer section 9.1 to set timezone
offset through serial configuration. Also, ensure that DST Mode if ON, there are proper settings of
DST parameters.
Apart from timezone offset, it is necessary that the setting of time format (UTC/LOCAL) should be
set to LOCAL. For setting this parameter to LOCAL, user can set it through front panel keypad
(parameter: “SET TIME FORMAT” as per section 9) or console based configuration utility as
section 9.2 or webserver as section 13.4 and snmp as per section 13.3 .
17.4 Cannot establish Serial communication with COM1
RS-232 cable used for serial communication with COM1 terminal should be cross cable as per
figure 10.1. The serial communication of end device should be 9600 (baud rate), 8 (Data bits), N
(NONE parity), 1 (1 stop bit). COM1 is used only to transmit NMEA serial time frame every
second. The device which will be using NMEA time frame from
mas
TER
T-Sync
Model MTS200
unit should comply with serial frame format as per table11.1.
17.5 Not able to receive time frame on COM1 terminal at every second
Refer troubleshoot index 17.4.
17.6 Cannot establish Serial communication with COM2
RS-232 cable used for serial communication with COM2 terminal should be cross cable as per
section 10.
Also, the serial communication parameters such as baudrate, parity, stop bits of COM2 terminal
are configurable through unit front panel keypad (refer section 9.1). It is necessary to match the
end device serial communication parameters as per configured in
mas
TER
T-Sync
Model
MTS200 unit.