10.2. SETTING TYPICAL CONFIGURATIONS
In order to facilitate this task, the instrument is provided with the following two pre-set
recording modes:
1. Default Configuration:
this is comprehensive which should fit most cases
.
2. Typical Configuration
: it is possible to select recording with pre-setting parameters for
the following situations:
EN50160
Setting parameters for Networks Quality in compliance with EN 50160
standard (see paragraph 16.11.2).
SURGES & DIPS
Setting parameters for Voltage Anomalies detection (surges, dips, break,
etc.) (See paragraph 16.10).
HARMONICS
Setting parameters for Harmonics Analysis of Voltage and Current (see
paragraph 16.11).
START-UP
Setting parameters for Start-Up motors and electrical devices.
POWER & ENERGY
Setting parameters for Power and Energy measures (see paragraph 16.12).
10.2.1. Default Configuration
The default configuration of instrument consists in the following parameters settings:
ANALYZER CONFIG:
System: SINGLE
Frequency: 50Hz
Current Range:
1000A
Clamp Type:
STD
TV Ratio:
1
Password: enabled
RECORDER CONFIG:
Start:
MANU (the recording is started
1 minute after pressing
the
START/STOP
key)
Stop: MANU
Integration period:
15min
Recording of harmonics:
ON
Recording of Voltage anomalies (voltage Sag and Surge) :
ON
Voltage Reference for Sag and Surge detection:
230V
Upper Limit for Sag and Surge detection:
6%
Lower Limit for Sag and Surge detection:
10%
Selected voltages:
V1
Selected voltage harmonics:
THD, 01, 03, 05, 07
Selected currents:
I1
Selected current harmonics:
THD, 01, 03, 05, 07
CO-GENERATION: OFF
Powers, Pf and cos
ϕ
selected:
P1
Q1i
Q1c
S1
Pf1
dpf1
Energies: Ea1
Eri1
Erc1
If the user changed the instrument’s settings, the user can quickly resume the above
configuration using the RESET option (see paragraph 5.4).