14.1.2. ANALYSER and AUX functions
VOLTAGE MEASUREMENT – SINGLE PHASE SYSTEM (AUTORANGE)
Range [V]
Resolution [V]
Accuracy
Input Impedance
15
-
310V
0.2V
±
(0.5% 2digit)
300k
Ω
(Phase - Neutral)
300k
Ω
(Phase - Phase)
310
-
600V
0.4V
VOLTAGE SAG AND SURGE DETECTION – SINGLE PHASE SYSTEM (MANUAL RANGE)
Range [V]
Resolution
(Voltage)
Resolution
(Time)
Accuracy
(Voltage)
Accuracy (rif. 50Hz)
(Time)
Input Impedance
15
-
310V
0.2V
10ms (½ period)
±
(1.0% 2digit)
±
10ms (½ period)
300k
Ω
(Phase -
Neutral)
300k
Ω
(Phase -
Phase)
30
-
600V
0.4V
CURRENT MEASUREMENT – SINGLE PHASE SYSTEM (AUTORANGE)
Range [V]
Resolution
[mV]
Accuracy
Input Impedance
Overload
Protection
0.005
-
0.26V 0.1
±
(0.5% 2digit)
200k
Ω
5V
0.26
-
1V 0.4
(*): Example: with a 1000A/1V full scale clamp , the instrument detect only current higher than 5A
POWER MEASUREMENT – SINGLE PHASE SYSTEM (AUTORANGE)
Quantity Range
Accuracy
Resolution
ACTIVE POWER
0
-
999.9W
1
-
999.9kW
1
-
999.9MW
1000
-
9999MW
±
(1.0%2digit)
0.1W
0.1kW
0.1MW
1MW
REACTIVE POWER
0
-
999.9VAR
1
-
999.9kVAR
1
-
999.9MVAR
1000
-
9999MVAR
0.1VAR
0.1kVAR
0.1MVAR
1MVAR
APPARENT POWER
0
-
999.9VA,
1
-
999.9kVA,
1
-
999.9MVA
1000
-
9999MVA
0.1VA
0.1kVA
0.1MVA
1MVA
ACTIVE ENERGY
(Classe2 EN61036)
0
-
999.9Wh,
1
-
999.9kWh,
1
-
999.9MWh
1000
-
9999MWh
0.1Wh
0.1kWh
0.1MWh
1MWh
REACTIVE ENERGY
(Classe3 IEC1268)
0
-
999.9VARh,
1
-
999.9kVARh,
1
-
999.9MVARh
1000
-
9999MVARh
0.1VARh
0.1kVARh
0.1MVARh
1MVARh
Cos
ϕ
MEASUREMENT – SINGLE PHASE SYSTEM
Cos
ϕ
Resolution
Accuracy [°]
0.20
0.01
0.6
0.50
0.7
0.80
1.0
VOLTAGE AND CURRENT HARMONICS MEASUREMENT – SINGLE PHASE SYSTEM
Range
Accuracy Resolution
DC – 25H
±
(5% + 2 digit)
0.1V / 0.1A
26H
– 33H
±
(10% + 2 digit)
34H
– 49H
±
(15% + 2 digit)
Harmonics values are null under fixed threshold:
- DC: its values are null if it is < 2%of Fundamental or is <2% of Full Scale clamp
- 1
st
Current Harmonic: its values are null if it is < 0.2% Full Scale clamp
- 2
nd
-
49
th
: its values are null if it is < 2% of fundamental or is <2% of Full Scale clamp
LEAKAGE CURRENT MEASUREMENT
Range (*)
Resolution
[mA]
Accuracy
Input Impedance
Overload Protection
0.5
-
999.9mA
0.1mA
±
(5% R 2digit)
200k
Ω
5V
(*): During a recording the instrument will detect only Current > 5mA with Resolution 1mA