This screen is displayed
when the phase
conductor has been
reversed with the neutral
one.
The instrument does not
perform the test.
Exchange the red cable
with the black one.
LOOP 05.06.01
- - -
Ω
---A
FRQ=50.0HZ
VP-N=231V VP-PE= 0V
CHANGE P-N
P-PE 50V
Phase and Neutral
Conductors are reversed.
FUNC Z2
Ω
UL
This screen is displayed
when the phase
conductor has been
exchanged with the
Protection Conductors.
The instrument does not
perform the test.
Exchange the red cable
with the green one.
LOOP 05.06.01
- - -
Ω
---A
FRQ=50.0HZ
VP-N= 1V VP-PE= 230V
CHANGE P-PE
P-N
Phase and Protection
Conductors are reversed.
FUNC Z2
Ω
This screen is displayed
when in a 230V Phase
to Phase System the
black conductor was
reversed with respect to
the green one.
The instrument does not
perform the test.
Reverse the black and
green conductors.
LOOP 05.06.01
- - -
Ω
---A
FRQ=50.0HZ
VP-N=131V VP-PE= 227V
CHANGE N-PE
P-N
Neutral and Protection
Conductors are reversed.
FUNC Z2
Ω