6.1.2. Measurement Procedure
1. Select the desired mode by means of the
F1
key.
2. Connect the red and black test leads to
B1
and
B4
input terminals respectively
B2
B3
B4
B1
Connection of the test leads during LOW
Ω
test.
3. If the cables supplied with the instrument are not long enough for the measurement
you can extend the black cable.
4. Short-circuit the test leads making sure that the conductive parts of the crocodiles
make a good contact to each other. Press the START key.
If the display doesn't
show 0.00
Ω
repeat the test leads calibration
(see paragraph 6.1.1).
5. Connect the instrument terminals to the ends of the conductor under test (see
previous picture).
6.
If the mode "RT+" or "RT-"
was selected use the
F3
,
F4
keys to set the
duration of the test.
7. Press the
START
key. The instrument will execute the measurement. In RT+/RT-
(Timer mode) you can press START key again if you want to stop the test before the
duration set is expired.
CAUTION
Never disconnect the test leads when the message
"MEASURING"
is
displayed.
6.1.3. Results of "AUTO" mode
At the end of the test, if
the
average resistance
value Ravg is lower
than 5
Ω
the instrument
emits a
double sound
signal
indicating the
positive outcome of
the test
and displays
one screen similar to the
screen alongside.
LOW
Ω
05.06.01
Average resistance value
(
Ravg)
1.05
Ω
R+ R-
1.07
Ω
1.03
Ω
219mA 219mA
AUTO 0.11
Ω
Resistance values and
corresponding test current
when the polarities of test
leads swapped.
FUNC
CAL
The displayed result can be stored pressing the
SAVE
key
twice
(according to
paragraph 9.1).