VR2250
Page 101 of 131
FREQUENCY
MEASUREMENT
Range [Hz]
Resolution [Hz]
Accuracy
47.0
-
63.6
0.1
±
(0.1%1 digit)
RCD and LOOP function are active only for 50Hz
±
0,5Hz frequency
VOLTAGE MEASUREMENT (RCD, LOOP, PHASE ROTATION)
Range [V]
Resolution [V]
Accuracy
0
-
460V
1
±
(3%R 2digit)
LOOP P-P, P-N: LINE IMPEDANCE MEASUREMENT (Phase
-
Phase, Phase
-
Neutral)
Range [
Ω
] Resolution
[
Ω
]*
Accuracy
0.01
-
9.99
10.0
-
199.9
0.01
0.1
±
(5% R 3digit)
(*) 0.1 m
Ω
on range 0.0
-
199.9 m
Ω
(with IMP57)
Peak value of the Test current
127V
3.65A
230V
6.64A
400V
11.5A
Voltage Range (Phase
-
Phase, Phase
-
Neutral)
100
-
250/ 100
-
440V
Frequency 50Hz
±
0.5Hz
LOOP P-PE: FAULT LOOP IMPEDANCE MEASUREMENT (Phase - Earth)
Range [
Ω
] Resolution
[
Ω
]*
Accuracy
0.01
-
19.99
20.0
-
199.9
200
-
1999
0.01
0.1
1
±
(5% R 3digit)
(*) 0.1 m
Ω
on range 0.0
-
199.9 m
Ω
(with IMP57)
Peak value of the Test current:
127V
3.65A
230V 6.64A
Voltage Range (Phase
-
Earth) 100
-
250V
Frequency 50Hz
±
0.5Hz
LOOP R
a 15mA
: FAULT LOOP IMPEDANCE MEASUREMENT without RCD Tripping (Phase - Earth)
Range [
Ω
] Resolution
[
Ω
]
Accuracy
1
÷
1999
1
- 0%, +(5% R 3digit)
Test Current
15mA
Voltage Range (Phase
-
Earth) 100
-
250V 50Hz
EARTH: GROUND RESISTANCE MEASUREMENT WITH EARTH RODS
Range RE [
Ω
]
Resolution [
Ω
]
Accuracy
0.01
-
19.99
20.0
-
199.9
200 - 1999
0.01
0.1
1
±
(5% R 3 digit)
Test Current
<10mA
-
77.5Hz
Open circuit Test Voltage
<20V RMS
RESISTIVITY MEASUREMENT
Range
ρ
Resolution
Accuracy
0.60
-
19.99
Ω
m
20.0
-
199.9
Ω
m
200
-
1999
Ω
m
2.00
-
99.99k
Ω
m
100.0
-
125.6k
Ω
m(*)
0.01
Ω
m
0.1
Ω
m
1
Ω
m
0.01 k
Ω
m
0.1 k
Ω
m
±
(5% R 3 digit)
(*) setting distance = 10m
Test Current
<10mA – 77.5Hz
Open circuit Test Voltage
<20V RMS