VR2250
Page 92 of 131
Current Range:
not modified
Clamp Type:
STD
TV Ratio:
not modified
Password: not
modified
RECORDER CONFIG:
Start:
MANU (the recording is started
1 minute after pressing
the
START/STOP
key)
Stop: MANU
Integration period:
10min
Recording of harmonics:
ON
Recording of Voltage anomalies (voltage Dips and Surge) :
OFF
Selected voltages:
V1
Sel. Harmonics voltage : THD,DC,01,03,05,07,09,11,13,15,17,19,21,23,25
Selected current:
I1
Sel. Harmonics current: THD,DC,01,03,05,07,09,11,13,15,17,19,21,23,25
CO-GENERATION: OFF
START-UP
ANALYZER CONFIG:
System: SINGLE
Frequency: 50Hz
Current Range:
not modified
Clamp Type:
STD
TV Ratio:
not modified
Password: not
modified
RECORDER CONFIG:
Start:
MANU (the recording is started
1 minute after pressing
the
START/STOP
key)
Stop: MANU
Integration period:
5sec
Recording of harmonics:
ON
Recording of Voltage anomalies (voltage Dips and Surge) :
ON
Voltage Reference for Dips and Surge detection:
230V
Upper Limit for Dips and Surge detection:
6%
Lower Limit for Dips and Surge detection:
10%
Selected voltages:
V1
Selected voltage harmonics:
THD, 01, 03, 05, 07, 09, 11, 13, 15
Selected currents:
I1
Selected current harmonics:
THD, 01, 03, 05, 07, 09, 11, 13, 15
CO-GENERATION: OFF
Powers, Pf and cos
ϕ
selected:
P1
Q1i
Q1c
S1
Pf1
dpf1
Energies: Ea1
Eri1
Erc1