3.0 Setup
Table 3-1, ME-ARC Compatibility Matrix (cont.)
Button
FEATURES/SETTINGS
Model/
Level
Required
Default
Setting
Main
Menu
Menu
Heading/
Item
Selections/
Adjustments Range
SETUP
02
Invert
Setup
(cont.)
02E AC-In
SOC
Connect SOC= 20-98%
≥
Level 3
[6]
50%
Disconnect SOC= 21-100%
100%
02F Power Up
Always
ON, OFF
≥
Level 1
Always
OFF
03
Char-
ger
Setup
03A AC Input
Amps
AC/AC1 Input= 5-60A
≥
Level 1 [1]
30A
AC2 Input= 5-60A
MSH-RE Models
20A
03B Battery
Type
Gel, Flooded, AGM, AGM2
≥
Level 1
Flooded:
Absorb (12.0-16.0)*
≥
Level 3
14.6*
Float (12.0-16.0)*
13.4*
EQ (12.0-16.0)*
15.5*
03C Max
Charge Rate
0-100%
≥
Level 3
100%
03D VAC
Dropout
AC/AC1 Input= 60-100
VAC, UPS Mode
U.S. Models
80 VAC
AC2 Input= 60-100 VAC
MSH-RE Models
75 VAC
110-190 VAC, UPS Mode
Export models
150 VAC
03E Absorb
Done
Time= 0.1-25.5 Hrs
≥
Level 4 [4]
2.0 Hrs
Amps= 0-150 ADC
≥
Level 4 [5]
SOC= 50-100%
≥
Level 4 [5] [6]
03F Max
Charge Time
0.0-25.5 Hrs
≥
Level 4 [5]
12.0
Hrs
03G Final
Charge Stage
Multi, Float, Silent
≥
Level 4 [5]
Multi
04
AGS
Setup
04A Gen Run
VDC
Start Gen Volts= 9.0-15.9*
≥
Level 1
11.5
Start Volts Delay= 0-127
sec, 1-127 min
120 Sec
Stop Gen Volts= 9.1-
16.0*, Float
14.4
Stop Volts Delay=0-127
sec, 1-127 min
120 Sec
04B Gen Run
Time
OFF, ON= Start Gen
Time= 12:00A-12:00P
≥
Level 1
OFF
Stop Gen Time= 12:00A-
12:00P
04C Gen Run
Amps
Start Gen AC Amps= OFF,
5-60A
≥
Level 4
OFF
Start Amps Delay= 0-127
sec, 1-127 min
Stop Gen AC Amps=
5-60A
Stop Amps Delay= 0-127
sec, 1-127 min
Custom
[2]