7.0 Using an AGS Module
88
© 2012 Magnum Energy, Inc.
7.7.3 AGS Remote Fault Statuses
The following “Fault” statuses indicate that the generator wasn’t able to start
based on an expected autostart condition. Refer to
Section 7.8.3
“Resolving
AGS Faults Using the Remote” for help in diagnosing the problem.
Table 7-4, AGS Remote Fault Statuses
STATUS
DESCRIPTION
Gen Run Fault
The generator successfully started and ran for more than
two minutes, but unexpectedly stopped before the AGS
could automatically stop the generator.
Fault Amp
The generator failed to start in Start Amps mode.
Fault Exercise
The generator failed to start in Start Exercise mode.
Fault SOC
The generator failed to start in Start SOC mode.
Fault Temp
The generator failed to start in Start Temp mode.
Fault Test
The generator failed to start in Test mode.
Fault Time
The generator failed to start in Start Time mode.
Fault Topoff
The generator failed to start in Start Topoff mode.
Fault VDC
The generator failed to start in Start VDC mode.
Fault MaxRn
The generator turned off because the
SETUP: 04F Max
Gen Run Time
setting had been met. This fault can occur
when: 1) an autostop parameter has been met, but it
did not stop the generator, or, 2) the autostop condition
exceeded the
Max Gen Run Time
setting.
Menu Items
Default Settings
Gen Run VDC
Start Volts: 11.5 VDC (12v)
Start Volts Delay: 120 Sec
Stop Volts: 14.4 VDC (12v)
Stop Volts Delay: 120 Sec
Gen Run Time
OFF
Gen Run Amps*
OFF
Gen Run SOC
OFF
Gen Run Temp
OFF
Max Gen Run Time
12.0 Hrs
Quiet Time
OFF
Gen Exercise
OFF
Gen Warm-up Time
60 Sec
Gen Cooldown Time
60 Sec
*MS-PAE, MS-PE and MSH Series models only
Table 7-5, AGS Default Settings on ME-ARC