7.0 Using an AGS Module
7.8.3 Resolving AGS Faults using the Remote
Should an AGS fault occur, use your ME-ARC remote and the information in
this section to resolve the issue.
• Gen Run Fault
– The generator successfully started and ran for more
than two minutes, but the generator unexpectedly stopped by itself be-
fore the active AGS autostop condition was
fi
nished.
Info:
The AGS module determines the generator is running by
monitoring the gen run sense voltage/signal. When this gen run
sense voltage/signal is no longer available, the AGS thinks the gen
is off or has stopped.
Info:
Gen run fault detection is not active if the generator is manu-
ally started.
Remedy:
A) If the generator is still running: Con
fi
rm you are getting the cor-
rect gen run sense signal to the AGS module. For assistance, refer
to your ME-AGS-N owner’s manual.
B) If the generator is not running: Check the generator for fault
codes and adequate fuel. If neither is an issue, check the genera-
tor’s owner’s manual for troubleshooting tips to determine why it
may have shut down on its own.
For the eight faults listed below, refer to the Remedy immediately following.
• Fault
Amp
– The generator failed to autostart and run per the
04C Gen
Run Amps
menu’s start parameters.
• Fault
Exercise
– The generator failed to autostart and run per the
04H
Gen Exercise
menu’s start parameters.
• Fault
SOC
– The generator failed to autostart and run per the
04D Gen
Run SOC
menu’s start parameters.
• Fault
Temp
– The generator failed to autostart and run per the
04 Start
Temp F
menu’s (ME-RC) or the
04E Gen Run Temp
menu’s (ME-ARC and
ME-RTR) start parameters.
• Fault
Test
– The generator failed to autostart and run after the red
TEST button is pressed on the AGS module.
Note:
The ME-ARC can be set to manually turn the generator on and off,
which can be used to test the generator wiring to the AGS.
• Fault
Time
– The generator failed to autostart and run per the
04B Gen
Run Time
menu’s start parameters.
• Fault
Topoff
– The generator failed to autostart and run per the
04G
Quiet Time Topoff
start parameters.
• Fault
VDC
– The generator failed to autostart and run per the
04A Gen
Run VDC
menu’s start parameters.
Remedy:
One of the above fault messages may display on the ARC
remote when:
A. The AGS attempts to start the generator four times, but the gen
failed to start and run per the speci
fi
c autostart parameters; or,
B. The generator started, but did not provide the correct gen run
sense signal to the AGS module. For either scenario, refer to your
ME-AGS-N owner’s manual.