7.0 Using an AGS Module
80
© 2012 Magnum Energy, Inc.
7.3.2.2 ME-ARC Remote’s AGS TECH Button
Press the ME-ARC’s TECH button, and rotate the SELECT knob to access:
TECH: 01 Temperatures
Press the SELECT knob, and then rotate the knob to display the current
temperature reading of the AGS’s remote temp sensor. If the remote temp
sensor is not installed, “
AGS TS Open
” displays.
TECH: 02 Revisions – AGS
Press the SELECT knob, and then rotate the knob until the AGS module soft-
ware version is shown on the screen (i.e.,
AGS: 5.2
).
Info:
The AGS may display a “
0.0
” revision for several reasons. Ei-
ther the AGS is not installed, there is no communication because of
a bad/miswired network cable, or the AGS is not powered or is bad.
TECH: 04 Fault History
Press the SELECT knob, rotate the knob until the
04B AGS Faults
menu dis-
plays, and then press the SELECT knob.
•
04B AGS Faults
–
This menu displays a history of the last nine AGS faults.
Information for each fault displays from the most recent fault (H1) to the
earliest/past recorded faults (H2 up to H9). Refer to Figure 7-1 below.
The top line displays the AGS fault mode. The bottom line displays the fault
history number, day(s) since this fault occurred, and the time this fault
occurred.
Rotate the SELECT knob to display additional readings for this fault (series of
three screens for each fault). The following information displays: DC voltage on
the AGS at the time of this fault, and the temperature of the AGS temperature
sensor at the time of this fault.
Continue to rotate the SELECT knob to display earlier faults (as applicable).
Time fault
occurred
Fault Temp
H1 D– 0 12:23AM
Fault Temp
H1 77F
Fault Temp
H1 14.2 VDC
Fault history
number
Day(s) since
fault occurred
AGS DC voltage
at time of fault
AGS temp
sensor at time
of fault
AGS fault
• 04C
Clear
Faults
– This menu
allows all recorded fault history infor-
mation—for any inverter and/or AGS that is network connected—to be
cleared/erased.
Figure 7-1, AGS Fault History Menu Items