3.0 Setup
•
No Ext Control
–
This menu indicates that the inverter/charger is not
being controlled externally.
•
####
– When this display shows a number or a series of numbers, it
indicates that one or more of the allowable functions of the inverter/
charger is currently being controlled externally. The number(s) displayed
can be used by Magnum technicians to determine what function(s) in the
inverter/charger is being controlled.
TECH: 07 Load Defaults
This menu restores factory defaults to all ME-ARC remote settings on
the inverter/charger and on any accessories that are network connected.
To restore, continually press the rotary SELECT knob until the ‘5.0 to 0.0
seconds’ countdown screen is
fi
nished and the screen displays “
DEFAULTS
LOADED”
. Refer to Table 3-4 for the remote’s default values for the inverter/
charger.
Info:
Refer to Table 7-5 for AGS defaults, or to Table 8-1 for BMK
defaults when connected to an ME-ARC.
Info:
If a PIN has been set and locked, it must be entered before
the
Load Defaults
menu can be used.
Table 3-4, Inverter/Charger Default Settings on ME-ARC
Menu Items
Default Settings
Search Watts
5 Watts
LowBatCutOut
10 VDC (12v)
20 VDC (24v)
40 VDC (48v)
AC In-Time
6:00A - 6:00P
AC In-VDC
11.0-14.1 VDC (12v)
22.0-28.2 VDC (24v)
44.0-56.4 VDC (48v)
Input Amps
30 Amps (AC1), 20 Amps (AC2)*
Battery Type
Flooded
Max Charge Rate
100%
VAC Dropout
80 VAC (AC1), 75 VAC (AC2)*
(Exports – 150 VAC)
Absorb Done
Time = 2 Hrs
Amps = 20 ADC
SOC = 100%
Max Charge Time
12.0 Hrs
Final Charge Stage
Multi
DC Volts to ReBulk
12.0 VDC
* AC2 settings available on MSH4024RE models only.