© 2012 Magnum Energy, Inc.
13
3.0 Setup
Table 3-1, ME-ARC Compatibility Matrix (cont.)
Button
FEATURES/SETTINGS
Model/
Level
Required
Default
Setting
Main
Menu
Menu
Heading/Item
Selections/
Adjustments Range
SETUP
04
AGS
Setup
(cont.)
04D Gen Run
SOC
OFF, Start Gen SOC= 20-90%
≥
Level 1
[6]
OFF
Stop Gen SOC= 21-100%
04E Gen Run
Temp
Start=OFF, Ext Input, 65-95F
(18-35C)
≥
Level 1
OFF
Time= 0.5-6.0 Hrs
04F Max Gen
Run Time
OFF, 0.1-25.5 Hrs
≥
Level 1
12.0 Hrs
04G Quiet Time
OFF, ON= Start Quiet Time=
12:00A-12:00P
≥
Level 1
OFF
Stop Quiet Time= 12:00A-
12:00P
Quiet Time Topoff=OFF, 30-
120 Min
04H Gen Ex-
ercise
Days=OFF, 1-255 days
≥
Level 1
OFF
Run Hour/Min/AM-PM=
12:00A-12:00P
Run Time= 0.0-25.5 Hrs
04I Gen Warm-
up Time
0-127 sec, 1-127 min
≥
Level 1
60 Sec
04J Gen
Cooldown time
0-127 sec, 1-127 min
≥
Level 1
60 Sec
05
BMK
Setup
05A Charge Eff
Auto, 50-97%
≥
Level 1
Auto
05B AmpHour
Size
200-2500 AH
≥
Level 1
400 AH
* 12-volt values shown; for 24v systems – x 2, for 48v systems – x 4.
** These settings return to the factory default setting when power to the re-
mote is removed.
ME-ARC Compatibility Matrix Notes:
[1] Not available on MM/MM-E/MM-AE/MMS/MMS-E models.
[2] AC Couple Mode can be activated using Battery Type: Custom with MS-PAE
Series
≥
Rev 4.1.
[3] The AC meter displays are only accurate when used with MS-PAE or MSH
Series inverters and aren’t shown unless the inverter is
≥
Level 4.
[4] Level 2 and 3 inverters can be used, but:
Level 2 inverters are limited from 1.0-4.5 hours,
Level 3 inverters <Rev 4.1 are limited from 1.0-6.5 hours,
Level 3 inverters
≥
Rev 4.1 (and MMS Rev 1.5) are limited from
1.5-6.5
hours;
Any setting outside these limited ranges are not recognized and
reverts to the inverter’s default absorption time (2.0 hrs).
[5] Requires
≥
Level 4 to display.
[6] SOC features require the ME-BMK (Battery Monitor Kit) to be installed.
[7] To manually turn generator “ON” with remote, ME-AGS-N Rev 5.2 or higher
is required.