7.0 Using an AGS Module
Table 7-2, AGS Remote Operational Statuses (cont.)
STATUS
DESCRIPTION
Quiet Time
The AGS has entered Quiet Time per the
SETUP: 04G
Quiet Time
setting.
Note:
The generator will not autostart during Quiet Time.
Ready
The
CTRL: 03 Gen Control
menu is set to
AUTO
, and the
AGS is ready to automatically start the generator based
on the active autostart settings under the
SETUP: 04
AGS Setup
menu.
STATUS
DESCRIPTION
Start Amp
The generator has started based on the
SETUP: 04C
Gen Run Amps
setting.
Start Exercise
The generator has started based on the
SETUP: 04H
Gen Exercise
setting.
Start SOC
The generator has started based on the
SETUP: 04D
Gen Run SOC
setting.
Start Temp
The generator has started based on the
SETUP: 04E
Gen Run Temp
setting.
Start Test
The AGS is in Test mode. Test mode may be started
from the TEST button located on the AGS,
Start Time
The generator has started based on the
SETUP: 04B
Gen Run Time
setting.
Start Topoff
The generator has started based on the
SETUP: 04G
Quiet Time Topoff Time
setting.
Start VDC
The generator has started based on
SETUP: 04A Gen
Run VDC
setting.
7.7.2 AGS Remote Start Statuses
The following “Start” statuses identify the condition that autostarted the
generator. If you determine that the autostart condition occurred sooner
than expected (or didn’t want this autostart condition), refer to the Setup
section for your speci
fi
c remote to change (or defeat) the autostart setting.
Table 7-3, AGS Remote Start Statuses