"Flowrate (using trickle flow)" - channel type
This channel uses the Mannings formula to calculate velocity in a circular pipe based upon depth
measurement from a MACE Area/Velocity sensor.
The Mannings equation, uses an algorithm to derive the "
Velocity
" of flow in a pipe based on depth, pipe
gradient and a "roughness coefficient".
V = (CoEff / N) R
h
2/3
.S
1/2
Where:
V
= Stream Velocity (ft/s, m/s)
CoEff
= 1.49 for US units and 1.0 for metric units
N
= Mannings roughness co-efficient (unitless)
R
h
= Hydraulic Radius (ft, m)
S
= Pipe slope (ft/ft, m/m).
WARNING: There are inherent inaccuracies with using the Mannings equation for
calculating "
Velocity
". User should make themselves aware of the limitations of this
method PRIOR to use.
Add a "Flowrate (using trickle flow)" - channel type
NOTE: The XCi implementation of the Mannings equation into a "
Flowrate (using
trickle flow)
" channel uses the derived "
Velocity
" measurement used in conjunction
with the "
Depth
" measurement ONLY from a MACE A/V Doppler sensor. A "
Flowrate
(using trickle flow)
" - channel type can only be added after suitable Doppler "Velocity
and "Depth" channels have been added to the configuration.
1. After selecting the ""
Flowrate (using trickle flow)
" channel type and naming the new channel, the
"
Select velocity channel
" dialogue box will appear prompting you to use the drop down list to
highlight the "
Velocity channel
" from which the new "
Flowrate (using trickle flow) channel
" will
receive its value.
2. Click “
Continue
” and the “
Select depth channel
” dialogue box will appear. In the “
Select depth
channel
” dialogue box use the drop down list to highlight the "
Depth
" channel from which the
"
Flowrate (using trickle flow)
" channel named will receive its value. Click “
Continue
” to complete
MACE XCi User Manual - 185 -
Содержание HVFlo XCi
Страница 1: ......
Страница 10: ...MACE XCi User Manual 10...
Страница 18: ...MACE XCi User Manual 18...
Страница 21: ...MACE XCi User Manual 21...
Страница 50: ...MACE XCi User Manual 50...
Страница 98: ...MACE XCi User Manual 98...
Страница 173: ...MACE XCi User Manual 173...
Страница 178: ...MACE XCi User Manual 178...
Страница 191: ...NOTE In the example the Net flowrate will be the sum of Flow Rate 1 Flow Rate 2 Flow Rate 3 MACE XCi User Manual 191...
Страница 211: ...For a short video of the procedure click Play MACE XCi User Manual 211...
Страница 233: ...5 Tighten all three screws 6 Reconnect the battery cable assembly to the backplane board MACE XCi User Manual 233...
Страница 238: ...3 Unscrew the locking ring using the tool and remove completely MACE XCi User Manual 238...
Страница 239: ...4 Remove the damaged ceramic depth sensor MACE XCi User Manual 239...
Страница 250: ...MACE XCi User Manual 250...