71
47DR OPERATING MANUAL EM-9509-B Rev.7
■
SETTING RANGE OF ANALOG OUTPUTS 0% AND 100%
The analog outputs 0% and 100% can be set within the range of -999.99 to 9999.99. The default values per input type are
as shown in the following tables.
The default values are 0000.00 for analog output 0%, and 0100.00 for 100%.
■
TEMPERATURE UNIT: °C
MAIN DISPLAY
FUNCTION
USABLE RANGE
CONFORMANCE RANGE
DEFAULT VALUE
TYPE 4
Pt 100 (JIS ’97, IEC)
-230.00 to +880.00
-200.00 to +850.00
Analog output 0%:
Analog output 100%:
TYPE 5
Pt 50 Ω (JIS ’81)
-230.00 to +679.00
-200.00 to +649.00
Analog output 0%:
Analog output 100%:
TYPE 7
Pt 1000
-230.00 to +880.00
-200.00 to +850.00
Analog output 0%:
Analog output 100%:
TYPE 1
JPt 100 (JIS ’89)
-230.00 to +530.00
-200.00 to +500.00
Analog output 0%:
Analog output 100%:
TYPE 3
Pt 100 (JIS ’89)
-230.00 to +680.00
-200.00 to +650.00
Analog output 0%:
Analog output 100%:
■
TEMPERATURE UNIT: °F
MAIN DISPLAY
FUNCTION
USABLE RANGE
CONFORMANCE RANGE
DEFAULT VALUE
TYPE 4
Pt 100 (JIS ’97, IEC)
-382.0 to +1616.0
-328.0 to +1562.0
Analog output 0%:
Analog output 100%:
TYPE 5
Pt 50 Ω (JIS ’81)
-382.0 to +1254.2
-328.0 to +1200.2
Analog output 0%:
Analog output 100%:
TYPE 7
Pt 1000
-382.0 to +1616.0
-328.0 to +1562.0
Analog output 0%:
Analog output 100%:
TYPE 1
JPt 100 (JIS ’89)
-382.0 to +986.0
-328.0 to +932.0
Analog output 0%:
Analog output 100%:
TYPE 3
Pt 100 (JIS ’89)
-382.0 to +1256.0
-328.0 to +1202.0
Analog output 0%:
Analog output 100%:
IMPORTANT
• The operational range of the DC output is -10 to +110% of the output span after analog output 0% and 100% adjust-
ments.
• The output is saturated at approximately -10% or +110%, or [max. value of the usable range + 20°C (+ 36°F)] or the
input corresponding to 0 Ω.
• The analog outputs 0% and 100% are returned to the previously set values per input type (or default values when the
input type is selected for the first time) when the input type has been changed.
• The analog outputs 0% and 100% can be set to any value, however it is recommended to use them within the usable
range.