47DR OPERATING MANUAL EM-9509-B Rev.7
3.2 OPERATING PROCEDURE
Procedures to change the input type ‘TYPE 4’ (default) to ‘TYPE 3’ (Pt 100 (JIS ’89)) are described here.
NOTE
The left figure shows a display example (default input
type). The display depends on the settings. Refer to 3.1
INPUT TYPE LIST for details.
1
Confirm the wiring, and turn on the power.
• All the indications turn on for approximately 3 seconds and then
the display moves on to Measuring Mode.
NOTE
• Indication ‘S.ERR’ may blink, which shows the input out of the meas-
uring range and does not show the unit failure.
• Indication ‘B.ERR’ may blink, which shows the input open or out of
the range and does not show the unit failure.
• The SD indicates the bank No. with the bank switching set to “ena-
bled”.
2
Hold down Init/
↑
button for 3 seconds or more to move on to
Initial Setting Mode.
• The input type is indicated.
• The SD indicates ‘RTTYPE’.
NOTE
Some alarm indicators turn on with the parameter display. The alarm indication is due to the last status before mode
transition held but does not show the unit failure.
3
Press Shift button to shift the display into the setting standby
mode.
• The indication ‘TYPE 4’ starts blinking, to which you can apply
changes.
5
2,5
3
4
■
Immediately after power on (all indicators on)
■
Measuring Mode
*
1 Display depends on the settings and input.
Blinking