215
47DR OPERATING MANUAL EM-9509-B Rev.7
37. APPENDICES
37.1 SPECIFICATIONS
■
GENERAL SPECIFICATIONS
Construction
Panel flush mounting
Degree of protection
IP66; Applicable to the front of the panel meter mounted according to the specified
panel cutout.
Connection
Input, excitation supply,
DC output, relay output,
network interface, power
M3 separable screw terminal (torque 0.6 N·m)
Photo MOSFET relay,
event trigger input
Euro Type Connector Terminal
Applicable wire size: max. 1.3 dia., 0.5 – 1.25 mm
2
, stripped length 7 to 8 mm
BCD output
50-pin connector (Honda Tsushin Kogyo HDR-EC50LFDT1-SLE+)
Screw terminal
Nickel-plated steel (standard) or stainless steel
Housing material
Flame-resistant resin (gray)
Isolation
Input or excitation supply to DC output to HH output or H output to L output or LL
output to network or BCD output or event trigger input to power
Burnout
Upscale standard; downscale optional by programming
Linearization
Standard
Infrared communication
Transmission distance max. 1 meter (for use with the COP-IRU)
Setting (front button)
Initial Setting mode
Input type, temperature unit, decimal point position, input compensation A input/
compensation value, input compensation B input/compensation value, bargraph
type, bargraph lower limit, bargraph upper limit, analog output type, analog output
function mode, analog output 0%, analog output 100%, analog output 0% adjust-
ment, analog output 100% adjustment
Alarm setting mode
Bank No., alarm output pattern, HH, H, L and LL alarm setpoint, HH, H, L and LL
trip action, HH, H, L and LL deadband (hysteresis), HH, H, L, LL and P ON delay
time, HH, H, L, LL and P OFF delay time, HH, H, L, LL and P one-shot output, HH,
H, L, LL and P coil at alarm, main display blinking at alarm, bank copy
Advanced setting mode
Event trigger mode, ON timing delay, OFF timing delay, startup timer, averaging
type, averaging time, low-end cutout, low-end cutout value, display color, automatic
return time to Measuring Mode, transition time to Lockout Setting Mode, burnout,
display refreshing rate, manual sub display reset, P output, latching alarm, alarm
power ON delay, standby sequence, alarm trip at over-range, round off low-digit
reading, display reading type, high-pass filter, backlight brightness, LCD contrast,
bank switching, REQ input logic, DAV output logic, DATA output logic, status output
logic, firmware version indication
Lockout setting mode
Alarm setting lockout, initial setting lockout, advanced setting lockout, Modbus
setting lockout, MAX/MIN display control lockout, loop test output lockout, IR com-
munication lockout, Modbus communication lockout, initialization
Modbus setting mode
Device address, baud rate, parity bit, stop bit, T1.5 timer, T3.5 timer, long register
Loop test output
----
Read rate
20 times/sec. (50 msec.)
Averaging
Simple average, moving average or no averaging
Lockout setting
Prohibiting certain operations; protecting settings