47DR OPERATING MANUAL EM-9509-B Rev.7
5. SETTING DECIMAL POINT POSITION
The decimal point position, 2 decimal places (‘00.0’), 1 decimal place (‘0.0’) or no decimal point (‘0’) can be selected. The
default value is 1 decimal place.
IMPORTANT
• The decimal point position of the current, MAX and MIN values, and the display digits of the BCD output depend on the
decimal point position setting.
• The decimal point position of the input comp. A input and comp. values, input comp. B input and comp. values, bargraph
lower and upper limits, analog output 0% and 100%, alarm setpoints, deadband, and low-end cutout value do not de-
pend on the decimal point position setting.
• “2 decimal places” is not selectable with °F.
5.1.1 OPERATING PROCEDURE
NOTE
• Procedures to change ‘0.0’ to ‘00.0’ are described here.
• To change to other decimal point positions, the proce-
dures are same.
1
Confirm the wiring, and turn on the power.
• All the indications turn on for approximately 3 seconds and then
the display moves on to Measuring Mode.
NOTE
• IIndication ‘S.ERR’ may blink, which shows the input out of the meas-
uring range and does not show the unit failure.
• Indication ‘B.ERR’ may blink, which shows the input open or out of
the range and does not show the unit failure.
• The SD indicates the bank No. with the bank switching set to “ena-
bled”.
3,6
2,3,
6
4
5
■
Immediately after power on (all indicators on)
■
Measuring Mode
*
1 Display depends on the settings and input.