10.2 ALARM SETPOINT
Alarm setpoints can be set within the range of -999.99 to 9999.99. However the alarm is not provided in setting the set-
point beyond the operational range of the input type. Set the setpoints within the valid range. All alarm setpoints of the
current bank No. are disabled (reset to ‘------’ status) when the input type has been changed.
10.2.1 ALARM SETPOINT DEFAULT VALUE
PARAMETER
DEFAULT VALUE
LL alarm setpoint
L alarm setpoint
H alarm setpoint
HH alarm setpoint
10.2.2 ALARM SETPOINT LIST
■
TEMPERATURE UNIT: °C
MAIN DISPLAY
FUNCTION
USABLE RANGE
CONFORMANCE RANGE
TYPE 4
Pt 100 (JIS ’97, IEC)
-230.00 to +880.00
-200.00 to +850.00
TYPE 5
Pt 50 Ω (JIS ’81)
-230.00 to +679.00
-200.00 to +649.00
TYPE 7
Pt 1000
-230.00 to +880.00
-200.00 to +850.00
TYPE 1
JPt 100 (JIS ’89)
-230.00 to +530.00
-200.00 to +500.00
TYPE 3
Pt 100 (JIS ’89)
-230.00 to +680.00
-200.00 to +650.00
■
TEMPERATURE UNIT: °F
MAIN DISPLAY
FUNCTION
USABLE RANGE
CONFORMANCE RANGE
TYPE 4
Pt 100 (JIS ’97, IEC)
-382.0 to +1616.0
-328.0 to +1562.0
TYPE 5
Pt 50 Ω (JIS ’81)
-382.0 to +1254.2
-328.0 to +1200.2
TYPE 7
Pt 1000
-382.0 to +1616.0
-328.0 to +1562.0
TYPE 1
JPt 100 (JIS ’89)
-382.0 to +986.0
-328.0 to +932.0
TYPE 3
Pt 100 (JIS ’89)
-382.0 to +1256.0
-328.0 to +1202.0
NOTE
• Alarm setpoints can be set also in Measuring Mode. Refer to 27. CONFIRMING AND CONFIGURING ALARM SET-
POINTS for details.
• The default values of the LL and HH setpoints are ‘------’ for dual alarm output option (SPDT relay, 2 points).
• The default values of all setpoints are ‘------’ for no alarm output option.