Installation, Operation, and Maintenance Manual

GP

D I M M I N G
P

A

N

E

L

4 0 0 0
S E R I E S  

C O N T R O L S

&

Содержание Grafik Eye GRX-4000 Series

Страница 1: ...Installation Operation and Maintenance Manual GP D I M M I N G P A N E L 4 0 0 0 S E R I E S C O N T R O L S...

Страница 2: ...LTER CHOKES TOP COVER SHIPPED IN BOTTOM OF CRATE PUNCH AS NEEDED CIRCUIT BREAKERS OUTPUT TERMINAL BLOCKS NEUTRAL BUS AND GROUND EARTH BAR MOUNTING SCREWS BEZEL FACEPLATE FEED LOAD AIR VENTS CONTROL WI...

Страница 3: ...es 22 23 Reference Sheets GP8 24 GP3 4 Step by Step Instructions Bel iev e it or not this is supposed to look like a dictionar y Thi s icon was created by Brent M Nye July 6 1995 Bel iev e it or not t...

Страница 4: ...vailable from Lutron Caution This equipment is air cooled vents must not be blocked or you will void the warranty Top View Bottom View Left Side Front View Right Side Suggested control wiring entry Ke...

Страница 5: ...ust not be blocked or you will void the warranty Note GP8 through 24 must have its top cover punched for Feed and Load Circuit wiring Mount Panels Top View Front View Right Side Left Side Bottom View...

Страница 6: ...earance Indoor Use Only NEMA Type 1 enclosure IP2O Relative Humidity 90 non condensing GP Panels must be mounted within 7 of true vertical Ceiling Weight w o Packaging 30 lbs 14kg 115 lbs 52kg 130 lbs...

Страница 7: ...s Control Units Control Interfaces or Circuit Selectors 33 maximum Total number of Control Unit addresses 8 maximum Note GRX 4116 4516 has 2 addresses GRX 4124 4524 has 3 addresses Total number of Wal...

Страница 8: ...to 1 2 to 2 3 to 3 To additional Control Units Wallstations Panels or Control Interfaces GP Panel STEP 3 Control Wiring continued Control Wiring To additional Single Scene Activators 2 12 AWG 2 5 mm2...

Страница 9: ...d to terminate Link B at the last panel DMX512 Stageboard on Link B Cable recommended by Stageboard manufacturer or from Lutron as GRX CBL DMX 250 500 GRX 4000 Series Control Unit GP Panel Circuit Sel...

Страница 10: ...jumper protects the dimmer from load faults STEP 4 Feed and Load Wiring continued Feed Wiring Mains Voltage Wiring IMPORTANT Panel GP3 277 V GP3 120 V 230 V GP4 GP8 through 24 Main Lugs GP 8 through 2...

Страница 11: ...r Eco 10 fluorescent dimming ballasts Dimmed Hot DH must be used for Non Dim loads Load Wiring For Hi lume FDB or Eco 10 Fluorescent Dimming Ballast DH SH H Load Terminals Dimmable Load or Non Dim Loa...

Страница 12: ...itch 1 8 requires knowledge of intended function Setting Switch 5 6 7 or 8 requires knowledge of intended function LUTRON 1 2 3 4 1 2 3 4 5 6 1 2 3 4 5 6 Caution Do not install controls in wallbox wit...

Страница 13: ...nd 14 Panic Control Fine Tuning Control Partition Status Control Zone Lockout Sequence Scenes 5 16 5 6 7 8 5 6 7 8 5 6 7 8 5 6 7 8 5 6 7 8 5 6 7 8 5 6 7 5 6 7 5 6 7 5 6 7 5 6 7 5 6 7 Input 1 Input 2 I...

Страница 14: ...rcuit breaker 1 ON The load should energize the breaker should not trip and total load current must be within the Circuit Breaker s limit and less than 16A D Repeat C for each circuit with completed l...

Страница 15: ...e buttons on Wallstations All GRX 4000 Series Control Units and Wallstations should act in parallel e g pressing scene 1 on a Wallstation will select scene 1 on all Control Units pressing a master rai...

Страница 16: ...there are no changes to be made go to Step 11 To change load types A Press and hold buttons 1 and 5 until SELECT VALUE LED blinks once per second B Press button 5 to step through the Value displays un...

Страница 17: ...exists push MASTER 5 and 6 buttons to have the address match these directories D Press and hold the top and bottom scene buttons until the scene LEDs stop cycling Repeat Steps A D on all GRX 4000 Seri...

Страница 18: ...but will only turn on and off A1 1 First zone of GRX 4000 Series Control Unit addressed A1 A 2 A 3 A 4 A 5 GP3 GP4 GP8 through 24 120V and 277V GP8 through 24 230V and 240V Danger Feed through panels...

Страница 19: ...hts C Select the primary zone assignment GRX 4000 Series Press button 3 or 4 to select both Control Unit and zone assignment Example If the control desired is addressed to A2 and the zone desired is t...

Страница 20: ...eginning of a fade from full With 5 LEDs the load will operate on a First On First Off basis Load turns ON at the beginning of a fade to full and OFF at the beginning of a fade from full Repeat Step B...

Страница 21: ...the minimum Low End and 99 is the maximum High End Value is a relative number It is not a intensity but rather a reference point to help set other circuits if desired Record the new trim setting on a...

Страница 22: ...eate an external sense line See Lutron Override ord Level is factory set to full output 100 If less than full output is needed contact Lutron Data A OK Data B OK Power 1 2 3 4 5 D C D Load Type High E...

Страница 23: ...set up a FADE to off time Press the OFF button and adjust FADE as desired STEP 18 Set up scenes on GRX 4000 Scenes are the preset light levels and fade times stored in the Control Unit To create a sce...

Страница 24: ...ed GRX PRG and GRX RS232 do not require this setup Control only 1 at a time GRX 4000 Series Control Unit NTGRX 4S NTGRX 4S IR GRX 4S DW EGRX 4S EGRX 4S IR EGRX 8S EGRX 8S IR GRX CIR w GRX IT 81T NTGRX...

Страница 25: ...r all 5 of the NTGRX 4M buttons Button 5 only turns ON or OFF it does not toggle To remove hold OFF button on the Control Unit until its LEDs go dark Press and hold Scene 1 on a Control Unit until its...

Страница 26: ...ll 800 523 9466 with any comments or suggestions Thank you for your help Congratulations Your state of the art dimming system is complete Place a copy of the Control Directory with each GP Panel Repla...

Страница 27: ...temporarily on page 8 Sb Save by Button TEMPORARY ZONES LED is normally ON and all intensity and fade changes are temporary unless the TEMPORARY ZONES LED is turned OFF with the TEMPORARY ZONES butto...

Страница 28: ...4 Control Unit requires three To ensure there are sufficient addresses available any GRX 4x16 and or GRX 4x24 Control Units in the system should be addressed first Assigning Zones When assigning zones...

Страница 29: ...ory as GRX 4000 Series Control Units are addressed and zones are assigned Keep this Directory for job records and maintenance information A7 A8 A5 A6 Zone A2 A2 A2 A2 A2 A2 A2 A2 1 2 3 4 5 6 7 8 Zone...

Страница 30: ...Go to the GRX 4000 Series Control Unit to be assigned to this circuit E Select Scene 1 F Identify the zone to be assigned to this circuit G Press the zone 6 button until all zone LEDs are off H Press...

Страница 31: ...dy been set proceed to Step D C Use button 3 or 4 to assign an address 1 512 to the Circuit Selector This address should match the address in the job drawing D Press and hold buttons 1 and 5 on the Ci...

Страница 32: ...nments of Link A and Link B Lowest intensity of the zone assignments of Link A and Link B Primary Link A b A A b b A A Secondary Link None None b b A A b b Application Example Circuit to follow Link A...

Страница 33: ...s selected go to Step G E Press button 5 until Load Type LED lights F Select Zone X 4000 Series on Secondary Link Press button 3 or 4 to select both Control Unit and zone assignment Example If the con...

Страница 34: ...5mm2 must be spliced to the Hot Live feed wire CHOKE DIMMER CARD TRANSFORMER DH 1 SH 1 H 1 DH 2 SH 2 H 2 DH 3 SH 3 H 3 CONTROL WIRING CHOKE DIMMER CARD TRANSFORMER DIMMED HOT NEUTRAL INPUT FEED INPUT...

Страница 35: ...R LOAD 16A MAX Note There is no Neutral bus on 230V or 240V panels Neutral terminals are included with the indexed load terminals 2 3 C 21 1 5 17 22 2 6 9 14 18 23 3 7 10 12 15 19 24 4 8 11 13 16 20 F...

Страница 36: ...HOT ORANGE SWITCHED HOT BLACK NEUTRAL WHITE TO DIMMING PANEL TO DIMMING PANEL TO DIMMING PANEL Hi lume FDB Eco 10 BALLAST BLUE Mount to Grounded Fixture LAMP LAMP LAMP RED YELLOW BLUE Hi lume FDB Eco...

Страница 37: ...ballasts will replace this ballast A Rapid Start one lamp ballast will normally have 6 wires 1 Hot 1 Neutral 4 lamp wires A 7th wire the Ground may be present depending upon the manufacturer New sock...

Страница 38: ...rom the tube 3 Transformers must be sized according to the chart These modified charts must be used by neon cold cathode transformer suppliers to size the transformer for dimming applications Stan dar...

Страница 39: ...26 22 18 16 15 13 13 10 10 X 20 100 11 10 10 8 X X X 14 13 12 11 9 8 X 4000 60 240 20 17 14 12 10 9 8 8 7 6 X 26 22 18 15 14 13 12 11 9 8 X 30 140 20 17 14 12 10 9 8 8 X X X 26 22 18 15 14 13 12 11 9...

Страница 40: ...1 per sec Flutter 5 per sec N A Off Off Off Off Circuit Display OK OUT LC OK OK OK OK OK N A OK OK OK Out Possible Cause Solutions All LEDs show OK see below for other suggestions Push any button on C...

Страница 41: ...ls The Circuit Selector can be used to view the intensity information being sent to the dimmer Use buttons 1 and 2 on the Circuit Selector to access the circuit Number desired Press button 5 repeatedl...

Страница 42: ...erly to prevent what may appear as dimming equipment malfunctions When lamps begin to fail on a circuit Lutron recommends group relamping of the entire circuit 2 New fluorescent lamps must be seasoned...

Страница 43: ...Thi s icon was created by Brent M Nye July 6 1995 Bel iev e it or not this is supposed to look like a dictionar y Thi s icon was created by Brent M Nye July 6 1995 Bel iev e it or not this is suppose...

Страница 44: ...l run only for a period of one year from the date of purchase and Lutron s obligations under this warranty are limited to remedying any defect or replacing any defective part and shall be effective on...

Отзывы: