Chapter 6 Communication Parameter
6-24
6.5 How to set the Transmission Standard
6.5.1 How to set
To operate the Cnet I/F module according to communication standard and mode defined by the user, follow the
lower steps. For example, the following example sets the XGL-CH2A (RS232 1 port, RS422 1port) equipped at the
base 0, slot 2 according the lower standard.
(1) Communication standard
(a) Channel 1: RS-232C, 9,600 Bps, 8/1/None, Null modem, XGT server, self station number 0
(b) Channel 2: RS-485, 9,600 Bps, 8/1/None, Null modem, Use P2P, self station number 10
(2) Execution sequence
(a) Read I/O Information
Read the IO information of the currently mounted modules by select [Online]-[Diagnosis]-[I/O Information
…
] then click
“
I/O Sync
”
,
(b) Standard settings
If the user double-clicks the Cnet I/F module mounted at the no. 8, standard settings shows. Write the items like
the lower figure.
Содержание XGL-C22A
Страница 74: ...Chapter 6 Communication Parameter 6 22 4 Click I O Sync 6 Read the message If there is no problem click OK ...
Страница 172: ...Chapter 8 Modbus Communication 8 23 ...
Страница 246: ...Chapter 10 Program Examples 10 40 XG 5000 program Sequence Program 1 2 3 4 ...
Страница 247: ...Chapter 10 Program Examples 10 41 Sequence Program 5 6 ...
Страница 289: ...Appendix A 23 Sub procedure module When port open event occurs perform the next module ...
Страница 291: ...Appendix A 25 The lower code shows BCC check setting ...
Страница 296: ...Appendix A 30 4 Example Register monitor X 5 Example execution monitor Y Address of server Monitor result ...
Страница 297: ...Appendix A 31 A 4 Dimension Unit mm XGL C22A CH2A C42A H W version Less than V2 0 H W version V2 0 or Later ...