Chapter 8 Modbus Communication
8-9
8.3.8 Force Single Coil (05)
(1) Writing single bit of output area
When writing single bit of output area, request and response frame is as follows.
Tail of frame is applied in case of ASCII mode.
(a) Request frame
Classification
Station no.
Function
code (05)
Address
Output
Frame error
check
Tail (CRLF)
Size (byte)
1
1
2
2
2
2
(b) Response frame (In case of receiving normal frame)
Classification
Station no.
Function
code (05)
Address
Output
Frame error
check
Tail (CRLF)
Size (byte)
1
1
2
2
2
2
(c) In case of response frame (In case of receiving abnormal frame)
Classification
Station no.
Error code
Exceptional code
Tail (CRLF)
Size (byte)
1
1
1
2
(2) Details of frame
(a) Station no.: indicates the station no. of slave to write single bit of output area.
(b) Function code: ‘05’ indicating Force Single Coil
(c) Address: start address of data to write and it consists of 2 byte. At this time, start address conforms to modbus
address regulation.
(d) Output: in case of turning on address set in the Address, FF00(Hex) is indicated and in case of turning off addres
set in the Address, it is indicated 0000(Hex).
(e) Frame error check: in case of ASCII mode, it uses LRC and in case of STU mode, it uses CRC. It consists of 2
byte.
(f) Tail: it is applies in case of ASCII mode, CRLF is added after LRC.
(g) No. of byte: no. of byte of response data
(h) Error code: error code is expressed by adding 80(Hex) to function code and in case of Force Single Coil, it is
expressed as 85(Hex).
(i) Exceptional code: indicates detail of error and consists of 1 byte
(3) Frame example
Example that turning on 9
th
bit to station number 1 server acting as Modbus RTU mode
(a) Request frame
Classification
Station
no.
Function
code
Address
Output
Error check
Upper byte
Lower byte
Upper byte
Lower byte
Frame
01
05
00
08
FF
00
CRC
(b) Response frame (In case receiving normal frame)
Classification
Station
no.
Function
code
Address
Output
Error check
Upper byte
Lower byte
Upper byte
Lower byte
Frame
01
05
00
08
FF
00
CRC
(c) Response frame (In case of receiving abnormal frame)
Classification
Station no.
Function code
Exceptional code
Error check
Frame
01
85
04
CRC
Содержание XGL-C22A
Страница 74: ...Chapter 6 Communication Parameter 6 22 4 Click I O Sync 6 Read the message If there is no problem click OK ...
Страница 172: ...Chapter 8 Modbus Communication 8 23 ...
Страница 246: ...Chapter 10 Program Examples 10 40 XG 5000 program Sequence Program 1 2 3 4 ...
Страница 247: ...Chapter 10 Program Examples 10 41 Sequence Program 5 6 ...
Страница 289: ...Appendix A 23 Sub procedure module When port open event occurs perform the next module ...
Страница 291: ...Appendix A 25 The lower code shows BCC check setting ...
Страница 296: ...Appendix A 30 4 Example Register monitor X 5 Example execution monitor Y Address of server Monitor result ...
Страница 297: ...Appendix A 31 A 4 Dimension Unit mm XGL C22A CH2A C42A H W version Less than V2 0 H W version V2 0 or Later ...