Chapter 7 XGT Dedicated Communication
7-26
4)
Selecting the active mode
Select ‘Use P2P settings’ to act as XGT client.
(b) Setting P2P parameter
No.
Type
Block form
Contents
1
Channel
Driver name changes according to driver set in the P2P Driver.
2
P2P
function
1. Read : when reading the destination station’s memory
2. Write: when writing self-station’s memory to destination station’s memory.
3
Conditional
flag
1. Determines when Cnet sends request frame
2. In case of XGK type Ex. : F90(20ms flag), M01
3. In case of XGI type Ex. : _T20MS(20ms flag), %MX01
4
Command
type
1. Single: When reading/writing max. 4 memory areas.
(Ex. : M01, M10, M20, M30)
2. Continuous: When reading/writing continuous memory areas.
(Ex. : M01~M10)
5
Data type
1. In case that command type is single:
bit, 1 byte, 2byte, 4 byte, 8 byte available
2. In case that command type is continuous:
1 byte, 2byte, 4 byte, 8 byte
6
No. of
variable
1. This is activated when command type is single and available max. no. is 4.
2. When command type is continuous, it is fixed as 1.
7
Data size
1. This is activated when command type is continuous.
2. When data type is 1 byte, available max. no. is 120 byte
8
Destination
station
1. Check: Specify the destination station
2. Uncheck: In case of using P2PSN command, communicate with previously
designated (P2PSN)destination station
9
Destination
station
number
1. Destination station number, setting range is 0~63.
10
Setting
1. When P2P function is Read
1)Read area : device area of server
2)Save area : client’s device to save the data from server
2. When P2P function is Write
1)Read area : device area of client
2)Save area : Server’s device area to save client’s data
Содержание XGL-C22A
Страница 74: ...Chapter 6 Communication Parameter 6 22 4 Click I O Sync 6 Read the message If there is no problem click OK ...
Страница 172: ...Chapter 8 Modbus Communication 8 23 ...
Страница 246: ...Chapter 10 Program Examples 10 40 XG 5000 program Sequence Program 1 2 3 4 ...
Страница 247: ...Chapter 10 Program Examples 10 41 Sequence Program 5 6 ...
Страница 289: ...Appendix A 23 Sub procedure module When port open event occurs perform the next module ...
Страница 291: ...Appendix A 25 The lower code shows BCC check setting ...
Страница 296: ...Appendix A 30 4 Example Register monitor X 5 Example execution monitor Y Address of server Monitor result ...
Страница 297: ...Appendix A 31 A 4 Dimension Unit mm XGL C22A CH2A C42A H W version Less than V2 0 H W version V2 0 or Later ...