Chapter 8 Modbus Communication
8-5
(c) In case of response frame (In case of receiving abnormal frame)
Frame
Station no.
Error code
Exceptional
code
Tail (CRLF)
Size
(byte)
1
1
1
2
(2) Details of frame
(a) Station no.: indicates the station no. of slave to read bit of output area.
(b) Function code: ‘01’ indicating Read Coil Status
(c) Address: start address of data to read and it consists of 2 byte. At this time, start address conforms to modbus
address regulation.
(d) Data size: size of data to read and it consists of 2 byte.
(e) Frame error check: in case of ASCII mode, it uses LRC and in case of STU mode, it uses CRC. It consists of 2
byte.
(f) Tail: it is applies in case of ASCII mode, CRLF is added after LRC.
(g) No. of byte: no. of byte of response data
(h) Data: makes address of request frame as start address and transmits data with byte unit
(i) Error code: error code is expressed by adding 80(Hex) to function code and in case of reading bit of output area,
it is expressed as 81(Hex).
(j) Exceptional code: indicates detail of error and consists of 1 byte
(3) Frame example
Example that requests reading bit of 20~28 to station number 1 server acting as modbus RTU mode
(a) Request frame
Classification
Station no.
Function
code
Address
Data size
Error check
Upper byte
Lower byte
Upper byte
Lower byte
Frame
01
01
00
13
00
13
CRC
(b) Response frame (In case receiving normal frame)
Classification
Station no.
Function
code
No. of byte
Data
Error check
Frame
01
01
03
12
31
05
CRC
(c) Response frame (In case of receiving abnormal frame)
Classification
Station no.
Function code
Exceptional code
Error check
Frame
01
81
02
CRC
Содержание XGL-C22A
Страница 74: ...Chapter 6 Communication Parameter 6 22 4 Click I O Sync 6 Read the message If there is no problem click OK ...
Страница 172: ...Chapter 8 Modbus Communication 8 23 ...
Страница 246: ...Chapter 10 Program Examples 10 40 XG 5000 program Sequence Program 1 2 3 4 ...
Страница 247: ...Chapter 10 Program Examples 10 41 Sequence Program 5 6 ...
Страница 289: ...Appendix A 23 Sub procedure module When port open event occurs perform the next module ...
Страница 291: ...Appendix A 25 The lower code shows BCC check setting ...
Страница 296: ...Appendix A 30 4 Example Register monitor X 5 Example execution monitor Y Address of server Monitor result ...
Страница 297: ...Appendix A 31 A 4 Dimension Unit mm XGL C22A CH2A C42A H W version Less than V2 0 H W version V2 0 or Later ...