Chapter 10 Program Examples
10-24
10.4 User - defined Communication
10.4.1 Communication with other producer’s product
When communication with device of which protocol is not supported by Cnet I/F module client, how to use user-defined
communication is described in the system like [Figure 10.3] below.
▶
System configuration
[Figure 10.3] configuration of user-defined communication system
▶
System configuration
Describes operation between Cnet I/F module and partner device (Temperature controller)
Device name
CPU
XGK-CPUH
Han-Young temperature controller
PX7
*note2)
Communication
module
XGL-CH2A
Operation mode
Client
Server
Protocol
User frame definition
PC Link
Type
RS-485
RS-485
Speed
9,600
9,600
Data bit
8
8
Stop bit
1
1
Parity bit
None
None
Station no.
0
1
Delay time
*note1)
100ms
-
Operation
Reads present value and setting value from temperature controller every second and
saves present value at %MB200 and setting value at %MB210.
Note 1) Delay time is set to prevent from frame error when communication with device of which response is slow in case of
RS-422/485 communication. It varies according to partner device and it has 50~100ms value generally.
Note 2) Please refer to (http://hynux.com) for the communication setting of the Han-young temperature controller by user
manual.
Содержание XGL-C22A
Страница 74: ...Chapter 6 Communication Parameter 6 22 4 Click I O Sync 6 Read the message If there is no problem click OK ...
Страница 172: ...Chapter 8 Modbus Communication 8 23 ...
Страница 246: ...Chapter 10 Program Examples 10 40 XG 5000 program Sequence Program 1 2 3 4 ...
Страница 247: ...Chapter 10 Program Examples 10 41 Sequence Program 5 6 ...
Страница 289: ...Appendix A 23 Sub procedure module When port open event occurs perform the next module ...
Страница 291: ...Appendix A 25 The lower code shows BCC check setting ...
Страница 296: ...Appendix A 30 4 Example Register monitor X 5 Example execution monitor Y Address of server Monitor result ...
Страница 297: ...Appendix A 31 A 4 Dimension Unit mm XGL C22A CH2A C42A H W version Less than V2 0 H W version V2 0 or Later ...