Chapter 4 Installation and Test Operation
4-4
4.4 Contents of Parameter Setting in the XG5000
Contents of parameter setting in XG5000 are as follows.
4.4.1 Basic setting parameter
Note
(1) Response waiting time: waiting time from sending to receiving
(a) Operation setting: Settable in case operation mode is Use P2P.
(b) basic response waiting time per communication speed
1) 9,600~115,200bps : 100ms+(setting value×100ms)
2) 7,200~2,400bps : 200ms+(setting value×100ms)
3) 1,800~1,200bps : 400ms+(setting value×100ms)
4) 600bps : 800ms+(setting value×100ms)
5) 300bps : 1,200ms+(setting value×100ms)
(2) Delay time setting: sends frame after delay time set by user
(a) Operation setting: settable in case communication type is RS-422/485
(3) Delay time between character: In case of character coming within set time at one frame, it means character
interval between character
(a) Operation setting: settable regardless of operation mode
Parameter
Lower
menu
Setting item
Setting range
Setting right
Reference
Client
Server
Basic
setting
Connection
setting
Communication type
RS-232C
RS-422
RS-485
○
○
Communication
speed (bps)
300~1,15,200
○
○
Data bit
7,8
○
○
Modbus ASCII
In case of
modbus,
data bit is 7.
Stop bit
1,2
○
○
Parity bit
NONE,ODD,EVEN
○
○
Modem type
Null modem, dedicated
modem, dial up modem
○
○
Modem initialization -
○
○
Setting available in
case of dial up
modem
STATION
0~31
○
○
No meaning in case
of client
Delay time
0~2550ms
○
-
Used in case of P2P
Time out
0~5000ms
○
-
Used in case of P2P
Operation
mode
Use P2P settings
Select one mode
○
-
XGT server
-
○
Modbus ASCII server
-
○
Modbus RTU server
-
○
Содержание XGL-C22A
Страница 74: ...Chapter 6 Communication Parameter 6 22 4 Click I O Sync 6 Read the message If there is no problem click OK ...
Страница 172: ...Chapter 8 Modbus Communication 8 23 ...
Страница 246: ...Chapter 10 Program Examples 10 40 XG 5000 program Sequence Program 1 2 3 4 ...
Страница 247: ...Chapter 10 Program Examples 10 41 Sequence Program 5 6 ...
Страница 289: ...Appendix A 23 Sub procedure module When port open event occurs perform the next module ...
Страница 291: ...Appendix A 25 The lower code shows BCC check setting ...
Страница 296: ...Appendix A 30 4 Example Register monitor X 5 Example execution monitor Y Address of server Monitor result ...
Страница 297: ...Appendix A 31 A 4 Dimension Unit mm XGL C22A CH2A C42A H W version Less than V2 0 H W version V2 0 or Later ...