Chapter 7 XGT Dedicated Communication
7-18
7.2.8 Error code of XGT communication
If XGT client transmits the request frame to server, server analyzes the received frame. If frame is suited for XGT protocol,
it transmits the ACK response frame and if frame is not suited for XGT protocol, it transmits the NAK response frame
including the error code.
The following table describes the error code included in the NAK response.
Error code is displayed as hex 2 byte (4 byte as ASCII code). The user can see error by frame monitor and in case of
viewing by ASCII, the user can see the following error code.
Error code
Error type
Error details and causes
Example
0003
Number of blocks
exceeded
Number of blocks exceeds 16 at Individual
Read/Write Request
01rSS1105%MW10…
0004
Variable length error Variable Length exceeds the max. size of 16
01rSS010D%MW10000000000
..
0007
Data type error
Other data type than X,B,W,D,L received
01rSS0105%MK10
0011
Data error
Data length area information incorrect
01rSB05%MW10%4
In case of start with other character than ‘%’
01rSS0105$MW10
Variable’s area value wrong
01rSS0105%MW^&
Other value is written for Bit Write than 00 or 01 01wSS0105%MX1011
0090
Monitor execution
error
Unregistered monitor execution requested
0190
Monitor execution
error
Reg. No. range exceeded
0290
Monitor reg. Error
Reg. No. range exceeded
1132
Device memory error Other letter than applicable device is input
1232
Data size error
Request exceeds the max range of 60 Words to
read or write at a time.
01wSB05%MW1040AA5512,..
1234
Extra frame error
Unnecessary details exist as added.
01rSS0105%MW10000
1332
Data type
discordant
All the blocks shall be requested of the identical
data type in the case of Individual Read/Write
01rSS0205%MW1005%MB10
1432
Data value error
Data value unavailable to convert to Hex
01wSS0105%MW10AA%5
7132
Variable request area
exceeded
Request exceeds the area each device
supports.
01rSS0108%MWFFFFF
Содержание XGL-C22A
Страница 74: ...Chapter 6 Communication Parameter 6 22 4 Click I O Sync 6 Read the message If there is no problem click OK ...
Страница 172: ...Chapter 8 Modbus Communication 8 23 ...
Страница 246: ...Chapter 10 Program Examples 10 40 XG 5000 program Sequence Program 1 2 3 4 ...
Страница 247: ...Chapter 10 Program Examples 10 41 Sequence Program 5 6 ...
Страница 289: ...Appendix A 23 Sub procedure module When port open event occurs perform the next module ...
Страница 291: ...Appendix A 25 The lower code shows BCC check setting ...
Страница 296: ...Appendix A 30 4 Example Register monitor X 5 Example execution monitor Y Address of server Monitor result ...
Страница 297: ...Appendix A 31 A 4 Dimension Unit mm XGL C22A CH2A C42A H W version Less than V2 0 H W version V2 0 or Later ...