Appendix
A-11
Device 1
Device 2
Type
Variable
Function
Description
F0050
-
WORD _SCAN_MAX
Max. scan time
Max. scan time displayed
F0051
-
WORD _SCAN_MIN
Min. scan time
Min. scan time displayed
F0052
-
WORD _SCAN_CUR
Present scan time
Present scan time displayed.
F0053
-
WORD _MON_YEAR
Month / Year
PLC’s time information (Month/Year)
F0054
-
WORD _TIME_DAY
Hour / Date
PLC’s time information (Hour/Date)
F0055
-
WORD _SEC_MIN
Second / Minute
PLC’s time information (Second/Minute)
F0056
-
WORD _HUND_WK
100 years / Day
PLC’s time information (100 years/Day)
F0057
-
WORD _FPU_INFO
FPU calculation
result
Floating decimal calculation result displayed.
F00570
BIT
_FPU_LFLAG_I
Incorrect error latch Latched if in incorrect error.
F00571
BIT
_FPU_LFLAG_U
Underflow latch
Latched if underflow found.
F00572
BIT
_FPU_LFLAG_O
Overflow latch
Latched if overflow found.
F00573
BIT
_FPU_LFLAG_Z
Latch divided by 0
Latched if divided by 0.
F00574
BIT
_FPU_LFLAG_V
Invalid calculation
latch
Latched if invalid calculation.
F0057A
BIT
_FPU_FLAG_I
Incorrect error
Reported if incorrect error found.
F0057B
BIT
_FPU_FLAG_U
Underflow
Reported if underflow found.
F0057C
BIT
_FPU_FLAG_O
Overflow
Reported if overflow found.
F0057D
BIT
_FPU_FLAG_Z
Division by 0
Reported if divided by 0.
F0057E
BIT
_FPU_FLAG_V
Invalid calculation
Reported if calculation invalid.
F0057F
BIT
_FPU_FLAG_E
Irregular value input Reported if irregular value input.
F0058
-
DWORD _ERR_STEP
Error step
Error step saved.
F0060
-
DWORD _REF_COUNT
Refresh
Increased when module refresh executed.
F0062
-
DWORD _REF_OK_CNT
Refresh OK
Increased if module refresh normal
F0064
-
DWORD _REF_NG_CNT
Refresh NG
Increased if module refresh abnormal.
F0066
-
DWORD _REF_LIM_CNT
Refresh LIMIT
Increased if module refresh abnormal (TIME
OUT).
F0068
-
DWORD _REF_ERR_CNT Refresh ERROR
Increased if module refresh abnormal.
F0070
-
DWORD
_MOD_RD_ERR_
CNT
Module READ
ERROR
Increased if module reads 1 word abnormally.
F0072
-
DWORD
_MOD_WR_ERR_
CNT
Module WRITE
ERROR
Increased if module writes 1 word abnormally.
F0074
-
DWORD _CA_CNT
Block service
Increased if module’s block data serviced
F0076
-
DWORD _CA_LIM_CNT
Block service LIMIT
Increased if module’s block data service
abnormal.
F0078
-
DWORD _CA_ERR_CNT
Block service
ERROR
Increased if module’s block data service
abnormal.
F0080
-
DWORD _BUF_FULL_CNT Buffer FULL
Increased if CPU’s internal buffer is FULL.
F0082
-
DWORD _PUT_CNT
PUT count
Increased if PUT executed.
F0084
-
DWORD _GET_CNT
GET count
Increased if GET executed.
F0086
-
DWORD _KEY
Present key
Local key’s present status displayed.
F0088
-
DWORD _KEY_PREV
Previous key
Local key’s previous status displayed.
Содержание XGL-C22A
Страница 74: ...Chapter 6 Communication Parameter 6 22 4 Click I O Sync 6 Read the message If there is no problem click OK ...
Страница 172: ...Chapter 8 Modbus Communication 8 23 ...
Страница 246: ...Chapter 10 Program Examples 10 40 XG 5000 program Sequence Program 1 2 3 4 ...
Страница 247: ...Chapter 10 Program Examples 10 41 Sequence Program 5 6 ...
Страница 289: ...Appendix A 23 Sub procedure module When port open event occurs perform the next module ...
Страница 291: ...Appendix A 25 The lower code shows BCC check setting ...
Страница 296: ...Appendix A 30 4 Example Register monitor X 5 Example execution monitor Y Address of server Monitor result ...
Страница 297: ...Appendix A 31 A 4 Dimension Unit mm XGL C22A CH2A C42A H W version Less than V2 0 H W version V2 0 or Later ...