Chapter 7 XGT Dedicated Communication
7-17
▷
In case that registration format of registration number is reading continuous device
Classifica
tion
Head
Station
no.
Instruction
Registrati
on no.
No. of
data
Data
Tail
Frame
check
Frame
ACK
10
Y(y)
09
04
9183AABB
ETX
BCC
Hex
h06
h3130
h59(79)
h3039
h3034
h3931383341414242
h03
2) In case of NAK response
Classific
ation
Head
Station no.
Instruction
Registration
no.
Error code
(Hex 2 byte)
Tail
Frame
check
Frame
NAK
10
Y(y)
09
1132
ETX
BCC
Hex
h15
h3130
h59(79)
h3039
h31313332
h03
(c) Example
The device registered in No.01 of the station No.1 is to be read.
It is supposed that the registered device is the device M000 with one block
1) XGT client: frame to execute monitor
Classification
Head
Station no.
Instruction
Registration no.
Tail
Frame check
Frame
ENQ
01
Y(y)
01
EOT
BCC
Hex
h05
h3031
h59(79)
h3031
h04
2) XGT server: response frame of execution of monitor
▷
In case of ACK
Classification Head
Station
no.
Instructio
n
Registratio
n no.
No. of
block
No. of
data
Data
Tail
Frame check
Frame
ACK
01
Y(y)
01
01
02
2342
ETX
BCC
Hex
h06 h3031 h59(79)
h3031
h3031
h3032 h32333432
h03
▷
In case of NAK
Classification
Head
Station no.
Instruction
Registration
no.
Error code
Tail
Frame check
Frame
NAK
01
Y(y)
01
Error code (2)
ETX
BCC
Hex
h15
h3031
h59(79)
h3031
Error code (4)
h03
Содержание XGL-C22A
Страница 74: ...Chapter 6 Communication Parameter 6 22 4 Click I O Sync 6 Read the message If there is no problem click OK ...
Страница 172: ...Chapter 8 Modbus Communication 8 23 ...
Страница 246: ...Chapter 10 Program Examples 10 40 XG 5000 program Sequence Program 1 2 3 4 ...
Страница 247: ...Chapter 10 Program Examples 10 41 Sequence Program 5 6 ...
Страница 289: ...Appendix A 23 Sub procedure module When port open event occurs perform the next module ...
Страница 291: ...Appendix A 25 The lower code shows BCC check setting ...
Страница 296: ...Appendix A 30 4 Example Register monitor X 5 Example execution monitor Y Address of server Monitor result ...
Страница 297: ...Appendix A 31 A 4 Dimension Unit mm XGL C22A CH2A C42A H W version Less than V2 0 H W version V2 0 or Later ...