Chapter 9 User-defined Communication
9-14
(b) Error
STAT
Message
Description
0
Initial state
Initial state before instruction operation
1
No error
normal operation
2
Module setting error
Module is not installed or CNET module trouble
3
Channel setting error
Input range(1, 2) is exceeded
4
Array size error
Transmit data size exceed 1024
5
Parameter setting error
CNET module’s parameter is not set as User defined or link enable is not
set
6
Instruction timeout error
No response from module or maximum scan time is exceeded(10 scan)
7
Version mismatch error
XGI CPU version is under V3.9, XGR CPU version is under V2.6 or
CNET module version is under V3.2
(c) Program example
Order to send up to 1,024 Byte with CNET module attached to BASE, SLOT