PROFINET interface
Leuze electronic GmbH + Co. KG
AMS 348
i
SSI
77
TNT
35/7-2
4V
9.9.3.2 Module 2: Static preset
PROFINET module identifier
Module ID
1002
Submodule ID
1
Description
With this module, a preset value can be specified. The specified preset value becomes active
in the position in which preset teaching is performed.
Note!
In the event of a device change, the preset value is retained in the PROFINET manager. The
preset value (preset teach) must, however, be activated again at the intended position.
Parameter
Input data
None
Output data
Parameter
Description
Rel.
addr
.
Data
type
Value
Default Unit
CR to
module
Metr. Inch
Preset
Preset value.
The value is accepted during a
corresponding teach event (see
Output data).
The resolution of the preset value
is independent of the resolution
selected in module 1.
0
sign
32 bit
-999999 … +999999
0
mm
in/
100
2b
4d
5d
Parameter length: 4 bytes
~
Output data Description
Rel.
addr
.
Data
type
Value
Default Unit
CR to
module
Metr. Inch
Preset
teach
Read in the preset value.
0.0 Bit
0
1 Preset teach
–
–
4d
5d
Preset reset Preset value is deactivated.
0.1 Bit
0
1 Preset reset
–
–
4d
5d
Output data length: 1 byte
Ä
Å