PROFINET interface
76
AMS 348
i
SSI
Leuze electronic GmbH + Co. KG
Note!
If the unit is changed from metric to inch (or vice versa), previously entered numerical values
(e.g. for offset, preset, limit values, etc.) are not automatically converted. This must be done
manually!
Example:
Preset = 10000mm -> Change from metric to inch -> Preset = 10000 inch/100
Input data
Output data
None
Offset
Output value = measurement
value+offset.
The parameter applies to all inter
-
faces.
Attention:
If the preset is activated, it has
priority over the offset. Preset and
offset are not offset against each
other.
The resolution of the offset value
is independent of the resolution
selected in module 1.
The entered offset applies imme
-
diately without any further
release.
1 - 4 sign
32 bit
-999999 … +999999
0
mm
in/100 –
Parameter length: 6 bytes
1) See following notice!
É
Input data
Description
Rel.
addr
.
Data
type
Value
Default Unit
CR to
module
Metr. Inch
Position
value
Output of the current position.
0
sign
32 bit
-999999 … +999999
–
Scaled
9a
Input data length: 4 bytes consistently
Ñ